Table of Contents

Program Version:EnergyPlus, Version 9.4.0-217a24fc09, YMD=2024.02.19 14:52

Tabular Output Report in Format: HTML

Building: Building

Environment: BRYANT GEOTHERMAL (01-01:31-12) ** MI_ANN-ARBOR-MUNI-AP - USA Custom-725374 WMO#=725374

Simulation Timestamp: 2024-02-19 14:52:40


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 109005.43 130.14 130.14
Net Site Energy 109005.43 130.14 130.14
Total Source Energy 170763.34 203.88 203.88
Net Source Energy 170763.34 203.88 203.88


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.250
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 837.58
Net Conditioned Building Area 837.58
Unconditioned Building Area 0.00


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 73803.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8298.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2400.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 7087.09 2024.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7465.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7924.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9170.74
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 25252.74 83752.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9170.74
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 73803.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 8298.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 2400.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 7087.09 2024.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 7465.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9170.74
  Water Heater 0.00 7924.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 18.82 97.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.95
Other 8.46 2.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 30.15 99.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.95


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 18.82 97.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.95
Other 8.46 2.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 30.15 99.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.95


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 25252.741 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 25252.741 100.00
     
Total On-Site and Utility Electric Sources 25252.741 100.00
Total Electricity End Uses 25252.741 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9170.74 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9170.74 100.00
Total Water End Uses 9170.74 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 2.00
Tolerance for Zone Cooling Setpoint Not Met Time 2.00


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 369.00
Time Setpoint Not Met During Occupied Cooling 86.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 4280.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

Zone Component Load Summary

| BLOCK:ZONE1 |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

General

Value
Program Version and Build EnergyPlus, Version 9.4.0-217a24fc09, YMD=2024.02.19 14:52
RunPeriod BRYANT GEOTHERMAL (01-01:31-12)
Weather File MI_ANN-ARBOR-MUNI-AP - USA Custom-725374 WMO#=725374
Latitude [deg] 42.22
Longitude [deg] -83.7
Elevation [ft] 820.25
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 936.09 200.02 268.03 200.02 268.03
Above Ground Wall Area [ft2] 936.09 200.02 268.03 200.02 268.03
Window Opening Area [ft2] 107.21 0.00 53.61 0.00 53.61
Gross Window-Wall Ratio [%] 11.45 0.00 20.00 0.00 20.00
Above Ground Window-Wall Ratio [%] 11.45 0.00 20.00 0.00 20.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 936.09 200.02 268.03 200.02 268.03
Above Ground Wall Area [ft2] 936.09 200.02 268.03 200.02 268.03
Window Opening Area [ft2] 107.21 0.00 53.61 0.00 53.61
Gross Window-Wall Ratio [%] 11.45 0.00 20.00 0.00 20.00
Above Ground Window-Wall Ratio [%] 11.45 0.00 20.00 0.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 837.58
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BLOCK:ZONE1 837.58 Yes Yes 6700.98 1.00 936.09 0.00 96.60 107.21 0.8529 500.05 1.5353
Total 837.58     6700.98   936.09 0.00 96.60 107.21 0.8529 500.05 1.5353
Conditioned Total 837.58     6700.98   936.09 0.00 96.60 107.21 0.8529 500.05 1.5353
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 15-JUN-17:10 29-JAN-06:10 - - - - - - - - - - 11-MAY-06:40
Heating 0.00 48.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 10.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 0.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1.00 0.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 13.23 49.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 48.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 10.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 0.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 1.00 0.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.02
  Water Heater 0.00 0.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 80003.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 26280.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7602.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 22444.82 2194.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23644.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 8589.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 79975.43 90787.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 95.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 31.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 9.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26.80 2.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 10.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 95.48 108.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 95.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 31.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 9.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26.80 2.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 10.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 95.48 108.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
BLOCK:ZONE1 SINGLE DUCT CAV NO REHEAT 1367.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:PackagedTerminalAirConditioner

Design Size Cooling Supply Air Flow Rate [ft3/min] Design Size Heating Supply Air Flow Rate [ft3/min] Design Size No Load Supply Air Flow Rate [ft3/min] Design Size Outdoor Air Flow Rate During Cooling Operation [ft3/min] Design Size Outdoor Air Flow Rate During Heating Operation [ft3/min] Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [ft3/min]
BLOCK:ZONE1 PTAC 1367.42 1367.42 1367.42 58.65 58.65 58.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
BLOCK:ZONE1 PTAC DX COOLING COIL 1367.42 4.45 0.708892
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
BLOCK:ZONE1 PTAC HEATING COIL 39145.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
BLOCK:ZONE1 PTAC SUPPLY FAN 1367.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
AIR LOOP 1367.42 1367.42 1367.42 1367.42 1367.42 1367.42 1.00 1.00 1367.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [ft3/min] Minimum Outdoor Air Flow Rate [ft3/min]
AIR LOOP AHU OUTDOOR AIR CONTROLLER 1367.42 58.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
AIR LOOP AHU HEATING COIL 38858.38
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [ft3/min]
AIR LOOP AHU SUPPLY FAN 1367.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP 0.003180 0.006362
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min] Design Power Consumption [Btu/h]
DHW LOOP SUPPLY PUMP 0.003180 0.145919
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [ft3/min] Tank Volume [ft3] Maximum Heater Capacity [Btu/h]
DHW LOOP WATER HEATER 0.003180 0.114520 910.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Zone Component Load Summary

For: BLOCK:ZONE1

Timestamp: 2024-02-19 14:52:40

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 317.73 88.67   214.76 621.16 3.66 837.58 2.53
Lights 28.58 146.68 0.00   175.25 1.03 837.58 0.71
Equipment 1028.73 147.06   0.00 1175.79 6.93 837.58 4.79
Refrigeration 0.00   0.00 0.00 0.00 0.00 837.58 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 837.58 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 3433.23     3567.87 7001.10 41.25 936.09 25.52
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   3226.03     3226.03 19.01 837.58 13.14
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 837.58 0.00
Exterior Wall   190.29     190.29 1.12 936.09 0.69
Interzone Wall   0.00     0.00 0.00 0.00  
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 936.09 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -201.9     -201.9 -1.2 837.58 -0.8
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 1640.28       1640.28 9.66 48.30 115.87
Fenestration Solar   3143.58     3143.58 18.52 48.30 222.07
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 6448.55 6740.46 0.00 3782.63 16971.64      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 17:00:00
Outside Dry Bulb Temperature [F] 86.57
Outside Wet Bulb Temperature [F] 73.22
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 70.99
Zone Relative Humidity [%] 65.98
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.01067
Supply Air Temperature [F] 45.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 473.03
Outside Air Flow [ft3/min] 58.65
Peak Sensible Load with Sizing Factor [Btu/h] 15108.71
Difference Due to Sizing Factor [Btu/h] 1970.70
Peak Sensible Load [Btu/h] 13138.01
Estimated Instant + Delayed Sensible Load [Btu/h] 13189.01
Difference Between Peak and Estimated Sensible Load [Btu/h] -51.0


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.1240
Airflow per Floor Area [ft3/min-ft2] 5.649E-01
Airflow per Total Capacity [ft3-h/min-Btu] 2.909E-03
Floor Area per Total Capacity [ft2-h/Btu] 5.544E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.804E+01
Number of People 1.7


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 837.58 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 837.58 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 837.58 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 837.58 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 837.58 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -17596.5     -2957.3 -20553.8 66.88 936.09 -74.9
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -2610.9     -2610.9 8.50 837.58 -10.6
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 837.58 0.00
Exterior Wall   -4775.3     -4775.3 15.54 936.09 -17.4
Interzone Wall   0.00     0.00 -0.00 0.00  
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 936.09 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   109.10     109.10 -0.4 837.58 0.44
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction -2901.5       -2901.5 9.44 48.30 -205.0
Fenestration Solar   0.00     0.00 -0.00 48.30 0.00
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -20498.0 -7277.2 0.00 -2957.3 -30732.5      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.30
Outside Wet Bulb Temperature [F] 0.30
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 70.99
Zone Relative Humidity [%] 21.48
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00343
Supply Air Temperature [F] 95.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 1093.93
Outside Air Flow [ft3/min] 58.65
Peak Sensible Load with Sizing Factor [Btu/h] -34755.1
Difference Due to Sizing Factor [Btu/h] -6951.0
Peak Sensible Load [Btu/h] -27804.1
Estimated Instant + Delayed Sensible Load [Btu/h] -27775.2
Difference Between Peak and Estimated Sensible Load [Btu/h] -28.9


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.0536
Airflow per Floor Area [ft3/min-ft2] 1.306E+00
Airflow per Total Capacity [ft3-h/min-Btu] -2.924E-03
Floor Area per Total Capacity [ft2-h/Btu] -2.410E-02
Total Capacity per Floor Area [Btu/h-ft2] -4.149E+01
Number of People 1.7



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 89.80 23.10 73.40 Wetbulb [F] 0.00 0.00
WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 0.30 0.00 0.30 Wetbulb [F] 393.70 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BLOCK:ZONE1_WALL_2_0_0 LOW PERFORMING PROJECT WALL R-11.5 0.30 0.088 0.096 268.03 214.42 90.00 90.00 E
BLOCK:ZONE1_WALL_3_0_0 LOW PERFORMING PROJECT WALL R-11.5 0.30 0.088 0.096 200.02 200.02 0.00 90.00 N
BLOCK:ZONE1_WALL_4_0_0 LOW PERFORMING PROJECT WALL R-11.5 0.30 0.088 0.096 268.03 214.42 270.00 90.00 W
BLOCK:ZONE1_WALL_5_0_0 LOW PERFORMING PROJECT WALL R-11.5 0.30 0.088 0.096 200.02 200.02 180.00 90.00 S
BLOCK:ZONE1_GROUNDFLOOR_0_0_0 PROJECT GROUND FLOOR 0.40 0.056 0.059 837.58 837.58 0.00 180.00  
BLOCK:ZONE1_ROOF_1_0_0 LOW PERFORMING PROJECT FLAT ROOF R-23.8 0.15 0.042 0.043 837.58 837.58 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
None                  


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
BLOCK:ZONE1_WALL_2_0_0_0_0_1_WIN PROJECT - U-0.55 - 1001 23.51 2.65 0.64 26.80 53.61 0.551 0.551 0.901 1.673 1.673 No BLOCK:ZONE1_WALL_2_0_0 90.00 90.00 E
BLOCK:ZONE1_WALL_4_0_0_0_0_1_WIN PROJECT - U-0.55 - 1001 23.51 2.65 0.64 26.80 53.61 0.551 0.551 0.901 1.673 1.673 No BLOCK:ZONE1_WALL_4_0_0 270.00 90.00 W
Total or Average           107.21 0.551 0.551 0.901              
North Total or Average           0.00 - - -              
Non-North Total or Average           107.21 0.551 0.551 0.901              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
BLOCK:ZONE1 GENERAL LIGHTING BLOCK:ZONE1 0.8529 837.58 714.39 General RESIDENTIAL LIGHT1 64.40 168.00 64.40 0.0000 Y 703.08
Interior Lighting Total   0.8529 837.58 714.39               703.08


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
Exterior Lighting Total 0.00           0.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
BLOCK:ZONE1 PTAC DX COOLING COIL Coil:Cooling:DX:SingleSpeed   53419.23 37868.44 15550.79 0.71 2.50    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
BLOCK:ZONE1 PTAC DX COOLING COIL   4.3 2.24 7.65 8.13 7.69 8.12
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
BLOCK:ZONE1 PTAC DX COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
BLOCK:ZONE1 PTAC HEATING COIL Coil:Heating:Electric   39145.21 1.00
AIR LOOP AHU HEATING COIL Coil:Heating:Fuel   38858.38 0.75


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
BLOCK:ZONE1 PTAC SUPPLY FAN Fan:OnOff 0.70 0.01 1367.42 92.20 0.07 1.00 3.87 General SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00
AIR LOOP AHU SUPPLY FAN Fan:ConstantVolume 0.60 0.05 1367.42 369.40 0.27 1.00 1.91 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
DHW LOOP SUPPLY PUMP Pump:VariableSpeed Intermittent 2.90 0.023795 0.04 1.80 0.90 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
DHW LOOP WATER HEATER WaterHeater:Mixed 0.11 910.11 0.80 6.81 6.83



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
BLOCK:ZONE1 13138.01 15108.71 18.04 473.032 543.987 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 71.01 70.99 0.01067 86.57 0.01451 58.652 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
BLOCK:ZONE1 27804.07 34755.09 41.49 1093.933 1367.416 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 71.01 70.99 0.00343 0.30 0.00082 58.652 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
AIR LOOP 543.99 543.99 1367.42 1367.42 1367.4158 1367.4158 1367.4158 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
BLOCK:ZONE1 PTAC DX COOLING COIL COIL:COOLING:DX:SINGLESPEED ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER BLOCK:ZONE1 PTAC 53419.234 37868.441 1367.415766 -999. -999.00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 unknown 6/15 17:00:00 53856.86 36143.20 1367.415766 72.67 63.93 0.01108507 44.78 44.78 0.00900000 86.57 0.01450644 72.58 4.2893 70.99 0.01067160 64.0448 15108.71 0.00 53445.47 37385.12
BLOCK:ZONE1 PTAC HEATING COIL COIL:HEATING:ELECTRIC ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER BLOCK:ZONE1 PTAC 39145.212 39145.212 -999. -999. -999.00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 39145.21 39145.21 1367.415766 67.96 49.10 0.00332284 95.00 60.95 0.00400000 0.30 0.00082114 0.30 4.2893 70.99 0.00343496 20.8497 34755.09 0.00 -999.0 -999.0
AIR LOOP AHU HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIR LOOP 38858.385 38858.385 -999. -999. -999.00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 38858.38 38858.38 1367.415766 67.96 49.10 0.00332284 95.00 66.79 0.00800000 0.30 0.00082114 0.30 4.2893 70.99 0.00343496 20.8497 27804.07 0.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BLOCK:ZONE1 4289.50 8658.17 4280.50
Facility 4289.50 8658.17 4280.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BLOCK:ZONE1 369.00 86.83 369.00 86.83
Facility 369.00 86.83 369.00 86.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
BLOCK:ZONE1 1.19 1.67 6700.98 0.158 1.930 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
BLOCK:ZONE1 1.19 1.67 6700.98 0.000 0.032 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Surfaces by Class

Total Outdoors
Wall 4 4
Floor 1 1
Roof 1 1
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 2 2
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 1
Conditioned Zones 1
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 814
Defaulted Fields 69
Fields with Defaults 1794
Autosized Fields 32
Autosizable Fields 35
Autocalculated Fields 11
Autocalculatable Fields 21



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
Electricity:Building 2778.72 226.13 01-JAN-00:10 473.19 01-JAN-21:10
Electricity:Zone:BLOCK:ZONE1 2778.72 226.13 01-JAN-00:10 473.19 01-JAN-21:10
InteriorLights:Electricity 703.09 20.94 01-JAN-00:10 209.38 01-JAN-21:10
InteriorLights:Electricity:Zone:BLOCK:ZONE1 703.09 20.94 01-JAN-00:10 209.38 01-JAN-21:10
General:InteriorLights:Electricity 703.09 20.94 01-JAN-00:10 209.38 01-JAN-21:10
InteriorEquipment:Electricity 2075.64 205.19 01-JAN-00:10 293.13 01-JAN-17:10
InteriorEquipment:Electricity:Zone:BLOCK:ZONE1 2075.64 205.19 01-JAN-00:10 293.13 01-JAN-17:10
General:InteriorEquipment:Electricity 2075.64 205.19 01-JAN-00:10 293.13 01-JAN-17:10
ElectricityPurchased:Facility 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
ElectricityPurchased:Plant 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
Cogeneration:ElectricityPurchased 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
General:Cogeneration:ElectricityPurchased 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
ElectricityNet:Plant 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
Cogeneration:ElectricityNet 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
General:Cogeneration:ElectricityNet 7395.92 226.14 13-FEB-01:30 3873.37 15-JUN-17:10
Electricity:HVAC 4616.92 0.00 01-JAN-01:10 3454.57 15-JUN-17:10
Fans:Electricity 2186.57 0.00 01-JAN-01:10 417.65 15-JUN-17:10
General:Fans:Electricity 2186.57 0.00 01-JAN-01:10 417.65 15-JUN-17:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 2430.34 0.00 01-JAN-00:10 3036.93 15-JUN-17:10
General:Cooling:Electricity 2430.34 0.00 01-JAN-00:10 3036.93 15-JUN-17:10
Electricity:Plant 0.27 0.01 13-FEB-01:40 0.04 01-JAN-07:10
Pumps:Electricity 0.27 0.01 13-FEB-01:40 0.04 01-JAN-07:10
General:Pumps:Electricity 0.27 0.01 13-FEB-01:40 0.04 01-JAN-07:10
WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 837.53 200.03 01-JAN-02:20 49284.34 29-JAN-06:10
NaturalGas:Building 20.25 200.03 01-JAN-00:10 285.76 01-JAN-17:10
NaturalGas:Zone:BLOCK:ZONE1 20.25 200.03 01-JAN-00:10 285.76 01-JAN-17:10
InteriorEquipment:NaturalGas 20.25 200.03 01-JAN-00:10 285.76 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:BLOCK:ZONE1 20.25 200.03 01-JAN-00:10 285.76 01-JAN-17:10
General:InteriorEquipment:NaturalGas 20.25 200.03 01-JAN-00:10 285.76 01-JAN-17:10
NaturalGas:HVAC 738.04 0.00 01-JAN-01:10 48398.71 29-JAN-05:10
Heating:NaturalGas 738.04 0.00 01-JAN-01:10 48398.71 29-JAN-05:10
General:Heating:NaturalGas 738.04 0.00 01-JAN-01:10 48398.71 29-JAN-05:10
NaturalGas:Plant 79.24 0.00 01-JAN-00:10 1340.52 01-JAN-08:10
WaterSystems:NaturalGas 79.24 0.00 01-JAN-00:10 1340.52 01-JAN-08:10
Water Heater:WaterSystems:NaturalGas 79.24 0.00 01-JAN-00:10 1340.52 01-JAN-08:10


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
Water:Plant 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
WaterSystems:Water 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
General:WaterSystems:Water 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
MainsWater:Facility 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
MainsWater:Plant 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
WaterSystems:MainsWater 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
General:WaterSystems:MainsWater 1226.13 0.00 02-JAN-01:30 0.00 11-MAY-06:40
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 146899.54 216.64 12-AUG-02:30 69052.83 29-JAN-05:10
EnergyTransfer:Building 64173.59 0.00 01-JAN-01:10 32183.45 29-JAN-05:10
EnergyTransfer:Zone:BLOCK:ZONE1 64173.59 0.00 01-JAN-01:10 32183.45 29-JAN-05:10
Heating:EnergyTransfer 53648.29 0.00 01-JAN-01:10 32183.45 29-JAN-05:10
Heating:EnergyTransfer:Zone:BLOCK:ZONE1 53648.29 0.00 01-JAN-01:10 32183.45 29-JAN-05:10
General:Heating:EnergyTransfer 53648.29 0.00 01-JAN-01:10 32183.45 29-JAN-05:10
Cooling:EnergyTransfer 10525.30 0.00 01-JAN-00:10 12766.66 15-JUN-17:00
Cooling:EnergyTransfer:Zone:BLOCK:ZONE1 10525.30 0.00 01-JAN-00:10 12766.66 15-JUN-17:00
General:Cooling:EnergyTransfer 10525.30 0.00 01-JAN-00:10 12766.66 15-JUN-17:00
EnergyTransfer:HVAC 77309.22 0.00 01-JAN-01:10 36299.03 29-JAN-05:10
HeatingCoils:EnergyTransfer 55352.64 0.00 01-JAN-01:10 36299.03 29-JAN-05:10
CoolingCoils:EnergyTransfer 21956.58 0.00 01-JAN-00:10 24574.79 15-JUN-17:10
EnergyTransfer:Plant 5416.73 216.64 12-AUG-02:30 976.87 26-FEB-20:10
WaterSystems:EnergyTransfer 5416.73 216.64 12-AUG-02:30 976.87 26-FEB-20:10
General:WaterSystems:EnergyTransfer 5416.73 216.64 12-AUG-02:30 976.87 26-FEB-20:10
PlantLoopHeatingDemand:Facility 5416.82 216.64 12-AUG-02:30 976.97 26-FEB-20:10
PlantLoopHeatingDemand:Plant 5416.82 216.64 12-AUG-02:30 976.97 26-FEB-20:10
WaterSystems:PlantLoopHeatingDemand 5416.82 216.64 12-AUG-02:30 976.97 26-FEB-20:10
General:WaterSystems:PlantLoopHeatingDemand 5416.82 216.64 12-AUG-02:30 976.97 26-FEB-20:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
BLOCK:ZONE1 0.000 -1270.16 58375.180 0.000 0.000 0.000 2846.602 2400.635 9111.975 10374.948 0.000 1896.729 0.167 0.000 -6529.94 0.000 -46784.33 -16439.68
Total Facility 0.000 -1270.16 58375.180 0.000 0.000 0.000 2846.602 2400.635 9111.975 10374.948 0.000 1896.729 0.167 0.000 -6529.94 0.000 -46784.33 -16439.68


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
BLOCK:ZONE1 15-JUN-17:07 -4544.2 -1.1 4544.24 0.00 0.00 0.00 340.44 428.64 1285.91 7491.33 0.00 3930.38 194.31 0.00 0.00 0.00 0.00 0.00
Total Facility 15-JUN-17:07 -4544.2 -1.1 4544.24 0.00 0.00 0.00 340.44 428.64 1285.91 7491.33 0.00 3930.38 194.31 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
BLOCK:ZONE1 29-JAN-08:03 0.00 0.00 40454.88 0.00 0.00 0.00 226.84 285.76 1028.73 0.00 0.00 0.00 0.00 0.00 -436.1 0.00 -19295.7 -22264.4
Total Facility 29-JAN-08:03 0.00 0.00 40454.88 0.00 0.00 0.00 226.84 285.76 1028.73 0.00 0.00 0.00 0.00 0.00 -436.1 0.00 -19295.7 -22264.4



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AIR LOOP 1367.4158 0.0000 1.6750 1.0000 58.6523 1367.4158 1.0000 1.0000 58.6523 0.0429    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AIR LOOP 1367.4158 0.0000 1.6750 1.0000 58.6523 1367.4158 0.0429 1.0000 58.6523 0.0429    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
BLOCK:ZONE1 AIR LOOP 4.999999 1.6750 0.060039 837.58 58.6523 1.0000 58.6523 1.000 58.6523


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
AIR LOOP 4.999999 1.67 0.060039 837.5818 58.6523 58.6523 58.6523


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BLOCK:ZONE1 AIR LOOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1367.4158 1367.4158 1367.4158 58.6523 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
AIR LOOP 1367.4158 1367.4158 1367.4158 1367.4158 58.6523 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BLOCK:ZONE1 AIR LOOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1367.4158 1367.4158 1367.4158 58.6523 0.0429 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
AIR LOOP 1367.4158 1367.4158 1367.4158 1367.4158 58.6523 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-02-19 14:52:40

Sec1.1A-General Information

Data
Weather File BRYANT GEOTHERMAL (01-01:31-12) ** MI_ANN-ARBOR-MUNI-AP - USA Custom-725374 WMO#=725374
Total gross floor area [ft2] 837.58
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
BLOCK:ZONE1 837.58 837.58 0.00 168.00
Totals 837.58 837.58 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 369.00
Number of hours cooling loads not met 86.83
Number of hours not met 455.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 738.04 48398.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 2430.34 3036.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 703.09 209.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- General 2075.64 293.13 20.25 285.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2186.57 417.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.27 0.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 79.24 1340.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 7087.09 25252.74
Natural Gas 2024.88 83752.68
Additional 0.00 0.00
Total 9111.97 109005.43


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.84
Space Heating 0.00
Space Cooling 2.90
Fans (All) 2.61
Service Water Heating 0.00
Receptacle Equipment 2.48
Miscellaneous (All) 8.83
Subtotal 8.83


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 25.81
Service Water Heating 2.77
Miscellaneous (All) 29.29
Subtotal 29.29


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 2.20
Space Heating 67.71
Space Cooling 7.61
Fans (All) 6.85
Service Water Heating 7.27
Receptacle Equipment 8.36
Miscellaneous 0.00


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
RESIDENTIAL OCC 6119. 8760.
COOLING FRACTION SCHEDULE 8760. 8760.
HEATING FRACTION SCHEDULE 8760. 8760.
HVAC AVAIL 6:00 - 8:00 18:00 - 22:00 EVERYDAY 2190. 2190.
RESIDENTIAL PLUG 7081. 8760.
RESIDENTIAL LIGHT1 3358. 8760.
RESIDENTIAL DHW 6424. 8760.
SUMMER (NORTHERN HEMISPHERE) - EDIT 4752. 4752.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
BLOCK:ZONE1 HEATING SETPOINT SCHEDULE BLOCK:ZONE1 DUAL SP January 69.01 365 69.01 365
BLOCK:ZONE1 COOLING SETPOINT SCHEDULE BLOCK:ZONE1 DUAL SP July 71.01 365 71.01 365