Table of Contents

Program Version:EnergyPlus, Version 9.4.0-217a24fc09, YMD=2024.05.02 13:51

Tabular Output Report in Format: HTML

Building: Building

Environment: BRYANT GEOTHERMAL (01-01:31-12) ** Ann Arbor Municipal MI USA TMY3 WMO#=725374

Simulation Timestamp: 2024-05-02 13:51:58


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 2916198.04 71.43 71.43
Net Site Energy 2916198.04 71.43 71.43
Total Source Energy 5890897.43 144.30 144.30
Net Source Energy 5890897.43 144.30 144.30


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.250
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 40823.98
Net Conditioned Building Area 40823.98
Unconditioned Building Area 0.00


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 68.49 1401867.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 256239.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 240811.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 466123.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 346950.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 289.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 203846.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 239055.50
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1310484.28 1605713.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 239055.50
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 633406.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 768460.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 68.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 256239.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 240811.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 466123.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 346950.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 289.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 239055.50
  Water Heater 0.00 203846.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 5.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 14.78 39.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.86
Other 11.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 32.10 39.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.86


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 5.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 14.78 39.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.86
Other 11.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 32.10 39.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.86


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1310484.281 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1310484.281 100.00
     
Total On-Site and Utility Electric Sources 1310484.281 100.00
Total Electricity End Uses 1310484.281 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 11484.46 6.17
Air to Air Heat Recovery for Heating 174534.43 93.83
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 186018.88 100.00


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 239055.50 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 239055.50 100.00
Total Water End Uses 239055.50 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 2.00
Tolerance for Zone Cooling Setpoint Not Met Time 2.00


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 206.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 793.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

Zone Component Load Summary

| BLOCK1:ZONE1XCAV | BLOCK1:ZONE5 | BLOCK1:ZONE3 | BLOCK1:ZONE6XCAV | BLOCK1:ZONE2XVAV | BLOCK1:ZONE4XVAV |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

General

Value
Program Version and Build EnergyPlus, Version 9.4.0-217a24fc09, YMD=2024.05.02 13:51
RunPeriod BRYANT GEOTHERMAL (01-01:31-12)
Weather File Ann Arbor Municipal MI USA TMY3 WMO#=725374
Latitude [deg] 42.22
Longitude [deg] -83.8
Elevation [ft] 839.94
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 20552.01 2775.27 7500.73 2775.27 7500.73
Above Ground Wall Area [ft2] 20552.01 2775.27 7500.73 2775.27 7500.73
Window Opening Area [ft2] 1185.12 150.01 240.02 150.01 645.06
Gross Window-Wall Ratio [%] 5.77 5.41 3.20 5.41 8.60
Above Ground Window-Wall Ratio [%] 5.77 5.41 3.20 5.41 8.60


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 20552.01 2775.27 7500.73 2775.27 7500.73
Above Ground Wall Area [ft2] 20552.01 2775.27 7500.73 2775.27 7500.73
Window Opening Area [ft2] 1185.12 150.01 240.02 150.01 645.06
Gross Window-Wall Ratio [%] 5.77 5.41 3.20 5.41 8.60
Above Ground Window-Wall Ratio [%] 5.77 5.41 3.20 5.41 8.60


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 40823.98
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BLOCK1:ZONE1XCAV 6120.60 Yes Yes 91813.44 1.00 3090.30 0.00 0.00 0.00 2.0470 149.92 3.4117
BLOCK1:ZONE5 4270.42 Yes Yes 64059.38 1.00 1035.10 0.00 68.76 76.51 2.0470 149.92 3.4117
BLOCK1:ZONE3 13601.33 Yes Yes 204029.87 1.00 6300.61 0.00 0.00 0.00 2.0470 149.92 3.4117
BLOCK1:ZONE6XCAV 5760.56 Yes Yes 86412.65 1.00 2940.29 0.00 216.22 240.02 2.0470 149.92 3.4117
BLOCK1:ZONE2XVAV 4800.47 Yes Yes 72010.54 1.00 3300.32 0.00 298.98 330.03 2.0470 149.92 3.4117
BLOCK1:ZONE4XVAV 6270.61 Yes Yes 94063.77 1.00 3885.38 0.00 491.49 538.55 2.0470 149.92 3.4117
Total 40823.98     612389.64   20552.01 0.00 1075.44 1185.12 2.0470 149.92 3.4117
Conditioned Total 40823.98     612389.64   20552.01 0.00 1075.44 1185.12 2.0470 149.92 3.4117
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 01-AUG-14:09 10-JAN-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 1130.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 340.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 75.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 132.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 117.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 72.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.44
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 664.82 1202.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.44


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 986.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 143.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 340.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 75.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 132.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 117.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.44
  Water Heater 0.00 72.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 216.92 1519624.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 811511.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 762651.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1476213.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1098792.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 917.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 220969.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4150303.72 1740593.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.01 37.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 18.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 36.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 26.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 5.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 101.66 42.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.01 37.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 18.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 36.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 26.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 5.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 101.66 42.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
BLOCK1:ZONE1XCAV SINGLE DUCT CAV NO REHEAT 5024.51
BLOCK1:ZONE5 SINGLE DUCT CAV NO REHEAT 3654.59
BLOCK1:ZONE3 SINGLE DUCT CAV NO REHEAT 10955.14
BLOCK1:ZONE6XCAV SINGLE DUCT CAV NO REHEAT 4972.79
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:Baseboard:RadiantConvective:Water

Design Size Maximum Water Flow Rate [gal/min] U-Factor times Area [Btu/h-F]
BLOCK1:ZONE1XCAV WATER RADIATOR 12.00 1575.22
BLOCK1:ZONE5 WATER RADIATOR 8.73 1143.86
BLOCK1:ZONE3 WATER RADIATOR 26.17 3442.72
BLOCK1:ZONE6XCAV WATER RADIATOR 11.88 1558.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [ft3/min] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [ft3/min] Design Size Maximum Flow per Zone Floor Area during Reheat [ft3/min-ft2] Design Size Maximum Flow Fraction during Reheat [] Design Size Maximum Reheat Water Flow Rate [gal/min] Design Size Reheat Coil Sizing Air Volume Flow Rate [ft3/min] Design Size Reheat Coil Sizing Inlet Air Temperature [F] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [lbWater/lbDryAir]
BLOCK1:ZONE2XVAV SINGLE DUCT VAV REHEAT 4687.29 0.153187 0.300000 1406.19 0.292987 0.300000 17.91 4687.29 60.01 0.008000
BLOCK1:ZONE4XVAV SINGLE DUCT VAV REHEAT 6048.77 0.155061 0.300000 1814.63 0.289447 0.300000 23.11 6048.77 60.01 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
BLOCK1:ZONE2XVAV SINGLE DUCT VAV REHEAT HEATING COIL 158587.80 17.91 1813.80
BLOCK1:ZONE4XVAV SINGLE DUCT VAV REHEAT HEATING COIL 204651.28 23.11 2340.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
AIR LOOP - RTU VAV 3220.82 3220.82 10736.06 10736.06 8107.19 10736.06 0.300000 1.00 10736.06
AIR LOOP - RTU CAV 9997.30 9997.30 9997.30 9997.30 9997.30 9997.30 1.00 1.00 9997.30
AIR LOOP - ERU CAV 14609.73 14609.73 14609.73 14609.73 14609.73 14609.73 1.00 1.00 14609.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [ft3/min]
AIR LOOP - RTU VAV AHU EXTRACT FAN 10736.06
AIR LOOP - RTU VAV AHU SUPPLY FAN 10736.06
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [ft3/min] Minimum Outdoor Air Flow Rate [ft3/min]
AIR LOOP - RTU VAV AHU OUTDOOR AIR CONTROLLER 10736.06 2141.30
AIR LOOP - RTU CAV AHU OUTDOOR AIR CONTROLLER 9997.30 2297.98
AIR LOOP - ERU CAV AHU OUTDOOR AIR CONTROLLER 14609.73 3456.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
AIR LOOP - RTU VAV AHU UNITARY COOLING COIL DX COOLING COIL 10736.06 35.78 0.701083
AIR LOOP - RTU CAV AHU UNITARY COOLING COIL DX COOLING COIL 9997.30 33.32 0.701083
AIR LOOP - ERU CAV AHU UNITARY COOLING COIL DX COOLING COIL 14609.73 48.69 0.701083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
AIR LOOP - RTU VAV AHU HEATING COIL 120645.68
AIR LOOP - RTU CAV AHU HEATING COIL 414545.86
AIR LOOP - ERU CAV AHU HEATING COIL 613214.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [ft3/min]
AIR LOOP - RTU CAV AHU EXTRACT FAN 9997.30
AIR LOOP - RTU CAV AHU SUPPLY FAN 9997.30
AIR LOOP - ERU CAV AHU EXTRACT FAN 14609.73
AIR LOOP - ERU CAV AHU SUPPLY FAN 14609.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [ft3/min]
AIR LOOP - ERU CAV AHU HEAT RECOVERY DEVICE 3456.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP 0.338687 0.677549
HW LOOP 13.34 26.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min] Design Power Consumption [Btu/h]
DHW LOOP SUPPLY PUMP 0.338687 15.54
HW LOOP SUPPLY PUMP 13.34 612.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [ft3/min] Tank Volume [ft3] Maximum Heater Capacity [Btu/h]
DHW LOOP WATER HEATER 0.338687 12.20 96922.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
BOILER 883883.59 99.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Zone Component Load Summary

For: BLOCK1:ZONE1XCAV

Timestamp: 2024-05-02 13:51:58

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 7044.51 1508.75   6233.83 14787.09 17.09 6120.60 8.24
Lights 1252.88 5621.61 0.00   6874.49 7.95 6120.60 3.83
Equipment 16705.14 2087.04   0.00 18792.17 21.72 6120.60 10.48
Refrigeration 0.00   0.00 0.00 0.00 0.00 6120.60 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 6120.60 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 5180.65     7976.38 13157.03 15.21 3090.30 14.53
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   30407.28     30407.28 35.15 6120.60 16.95
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 6120.60 0.00
Exterior Wall   20691.80     20691.80 23.92 3090.30 22.85
Interzone Wall   -999.6     -999.6 -1.2 3090.30 -1.1
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 3090.30 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -17202.4     -17202.4 -19.9 6120.60 -9.6
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 0.00       0.00 0.00 0.00  
Fenestration Solar   0.00     0.00 0.00 0.00  
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 30183.17 42114.47 0.00 14210.21 86507.85      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 17:00:00
Outside Dry Bulb Temperature [F] 86.55
Outside Wet Bulb Temperature [F] 73.22
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 73.99
Zone Relative Humidity [%] 55.29
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00988
Supply Air Temperature [F] 53.99
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 3380.38
Outside Air Flow [ft3/min] 1183.81
Peak Sensible Load with Sizing Factor [Btu/h] 83006.92
Difference Due to Sizing Factor [Btu/h] 10826.99
Peak Sensible Load [Btu/h] 72179.93
Estimated Instant + Delayed Sensible Load [Btu/h] 72297.64
Difference Between Peak and Estimated Sensible Load [Btu/h] -117.7


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.3502
Airflow per Floor Area [ft3/min-ft2] 5.524E-01
Airflow per Total Capacity [ft3-h/min-Btu] 3.784E-03
Floor Area per Total Capacity [ft2-h/Btu] 7.374E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.356E+01
Number of People 40.8


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 6120.60 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 6120.60 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 6120.60 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 6120.60 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 6120.60 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -33037.7     -6005.4 -39043.2 42.90 3090.30 -43.1
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -28975.0     -28975.0 31.84 6120.60 -16.2
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 6120.60 0.00
Exterior Wall   -20449.5     -20449.5 22.47 3090.30 -22.6
Interzone Wall   1681.09     1681.09 -1.8 3090.30 1.86
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 3090.30 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   -4218.5     -4218.5 4.64 6120.60 -2.4
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction 0.00       0.00 -0.00 0.00  
Fenestration Solar   0.00     0.00 -0.00 0.00  
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -33037.7 -51961.9 0.00 -6005.4 -91005.1      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.32
Outside Wet Bulb Temperature [F] 0.32
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 71.99
Zone Relative Humidity [%] 22.28
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00369
Supply Air Temperature [F] 52.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 4019.61
Outside Air Flow [ft3/min] 1183.81
Peak Sensible Load with Sizing Factor [Btu/h] -106310.5
Difference Due to Sizing Factor [Btu/h] -21262.1
Peak Sensible Load [Btu/h] -85048.4
Estimated Instant + Delayed Sensible Load [Btu/h] -84999.6
Difference Between Peak and Estimated Sensible Load [Btu/h] -48.8


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.2945
Airflow per Floor Area [ft3/min-ft2] 6.569E-01
Airflow per Total Capacity [ft3-h/min-Btu] -3.513E-03
Floor Area per Total Capacity [ft2-h/Btu] -5.757E-02
Total Capacity per Floor Area [Btu/h-ft2] -1.737E+01
Number of People 40.8



Table of Contents

Report: Zone Component Load Summary

For: BLOCK1:ZONE5

Timestamp: 2024-05-02 13:51:58

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 4914.92 1588.17   4349.60 10852.68 15.96 4270.42 8.67
Lights 874.15 5887.15 0.00   6761.30 9.94 4270.42 5.40
Equipment 11655.38 2196.95   0.00 13852.33 20.37 4270.42 11.07
Refrigeration 0.00   0.00 0.00 0.00 0.00 4270.42 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 4270.42 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 3614.41     5699.74 9314.16 13.69 1035.10 30.70
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   21308.02     21308.02 31.33 4270.42 17.02
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 4270.42 0.00
Exterior Wall   3622.01     3622.01 5.33 1035.10 11.94
Interzone Wall   5659.51     5659.51 8.32 13066.28 1.48
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 1035.10 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -5106.5     -5106.5 -7.5 4270.42 -4.1
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 642.05       642.05 0.94 68.76 31.86
Fenestration Solar   1106.80     1106.80 1.63 68.76 54.92
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 21700.92 36262.17 0.00 10049.34 68012.42      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 17:00:00
Outside Dry Bulb Temperature [F] 86.55
Outside Wet Bulb Temperature [F] 73.22
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 73.99
Zone Relative Humidity [%] 54.70
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00978
Supply Air Temperature [F] 53.99
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 2709.75
Outside Air Flow [ft3/min] 825.96
Peak Sensible Load with Sizing Factor [Btu/h] 66539.40
Difference Due to Sizing Factor [Btu/h] 8679.05
Peak Sensible Load [Btu/h] 57860.35
Estimated Instant + Delayed Sensible Load [Btu/h] 57963.08
Difference Between Peak and Estimated Sensible Load [Btu/h] -102.7


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.3048
Airflow per Floor Area [ft3/min-ft2] 6.347E-01
Airflow per Total Capacity [ft3-h/min-Btu] 3.784E-03
Floor Area per Total Capacity [ft2-h/Btu] 6.418E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.558E+01
Number of People 28.5


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 4270.42 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 4270.42 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 4270.42 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 4270.42 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 4270.42 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -23050.9     -4206.9 -27257.8 41.28 1035.10 -89.8
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -20629.7     -20629.7 31.24 4270.42 -16.5
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 4270.42 0.00
Exterior Wall   -6446.3     -6446.3 9.76 1035.10 -21.2
Interzone Wall   -8206.1     -8206.1 12.43 13066.28 -2.1
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 1035.10 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   -1524.0     -1524.0 2.31 4270.42 -1.2
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction -1968.8       -1968.8 2.98 68.76 -97.7
Fenestration Solar   0.00     0.00 -0.00 68.76 0.00
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -25019.7 -36806.2 0.00 -4206.9 -66032.8      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.32
Outside Wet Bulb Temperature [F] 0.32
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 71.99
Zone Relative Humidity [%] 22.35
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00370
Supply Air Temperature [F] 52.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 2923.67
Outside Air Flow [ft3/min] 825.96
Peak Sensible Load with Sizing Factor [Btu/h] -77325.1
Difference Due to Sizing Factor [Btu/h] -15465.0
Peak Sensible Load [Btu/h] -61860.1
Estimated Instant + Delayed Sensible Load [Btu/h] -61825.9
Difference Between Peak and Estimated Sensible Load [Btu/h] -34.2


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.2825
Airflow per Floor Area [ft3/min-ft2] 6.848E-01
Airflow per Total Capacity [ft3-h/min-Btu] -3.513E-03
Floor Area per Total Capacity [ft2-h/Btu] -5.523E-02
Total Capacity per Floor Area [Btu/h-ft2] -1.811E+01
Number of People 28.5



Table of Contents

Report: Zone Component Load Summary

For: BLOCK1:ZONE3

Timestamp: 2024-05-02 13:51:58

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 15654.44 3290.98   13852.98 32798.40 18.10 13601.33 8.23
Lights 2784.17 12268.39 0.00   15052.57 8.31 13601.33 3.78
Equipment 37122.52 4552.37   0.00 41674.89 23.00 13601.33 10.45
Refrigeration 0.00   0.00 0.00 0.00 0.00 13601.33 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 13601.33 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 12255.96     17519.64 29775.60 16.43 6300.61 16.12
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   74470.43     74470.43 41.10 13601.33 18.68
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 13601.33 0.00
Exterior Wall   17958.01     17958.01 9.91 6300.61 9.72
Interzone Wall   -936.8     -936.8 -0.5 5100.50 -0.6
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 6300.61 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -29616.5     -29616.5 -16.3 13601.33 -7.4
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 0.00       0.00 0.00 0.00  
Fenestration Solar   0.00     0.00 0.00 0.00  
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 67817.09 81986.88 0.00 31372.62 181176.60      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 16:30:00
Outside Dry Bulb Temperature [F] 87.48
Outside Wet Bulb Temperature [F] 73.48
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 73.99
Zone Relative Humidity [%] 55.58
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00994
Supply Air Temperature [F] 53.99
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 7003.75
Outside Air Flow [ft3/min] 2630.69
Peak Sensible Load with Sizing Factor [Btu/h] 171980.76
Difference Due to Sizing Factor [Btu/h] 22432.27
Peak Sensible Load [Btu/h] 149548.49
Estimated Instant + Delayed Sensible Load [Btu/h] 149803.98
Difference Between Peak and Estimated Sensible Load [Btu/h] -255.5


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.3756
Airflow per Floor Area [ft3/min-ft2] 5.150E-01
Airflow per Total Capacity [ft3-h/min-Btu] 3.784E-03
Floor Area per Total Capacity [ft2-h/Btu] 7.909E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.264E+01
Number of People 90.7


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 13601.33 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 13601.33 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 13601.33 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 13601.33 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 13601.33 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -73417.1     -13320.3 -86737.3 43.66 6300.61 -47.0
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -64298.7     -64298.7 32.37 13601.33 -16.1
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 13601.33 0.00
Exterior Wall   -41945.0     -41945.0 21.12 6300.61 -22.7
Interzone Wall   2874.51     2874.51 -1.4 5100.50 1.92
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 6300.61 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   -8539.8     -8539.8 4.30 13601.33 -2.1
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction 0.00       0.00 -0.00 0.00  
Fenestration Solar   0.00     0.00 -0.00 0.00  
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -73417.1 -111909.0 0.00 -13320.3 -198646.3      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.32
Outside Wet Bulb Temperature [F] 0.32
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 71.99
Zone Relative Humidity [%] 22.25
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00368
Supply Air Temperature [F] 52.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 8764.11
Outside Air Flow [ft3/min] 2630.69
Peak Sensible Load with Sizing Factor [Btu/h] -231792.9
Difference Due to Sizing Factor [Btu/h] -46358.6
Peak Sensible Load [Btu/h] -185434.3
Estimated Instant + Delayed Sensible Load [Btu/h] -185326.1
Difference Between Peak and Estimated Sensible Load [Btu/h] -108.2


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.3002
Airflow per Floor Area [ft3/min-ft2] 6.445E-01
Airflow per Total Capacity [ft3-h/min-Btu] -3.513E-03
Floor Area per Total Capacity [ft2-h/Btu] -5.868E-02
Total Capacity per Floor Area [Btu/h-ft2] -1.704E+01
Number of People 90.7



Table of Contents

Report: Zone Component Load Summary

For: BLOCK1:ZONE6XCAV

Timestamp: 2024-05-02 13:51:58

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 6630.13 1435.15   5867.13 13932.41 15.69 5760.56 8.25
Lights 1179.18 5336.04 0.00   6515.22 7.34 5760.56 3.86
Equipment 15722.48 1985.23   0.00 17707.71 19.95 5760.56 10.49
Refrigeration 0.00   0.00 0.00 0.00 0.00 5760.56 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 5760.56 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 4875.91     7630.37 12506.27 14.09 2940.29 14.51
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   28786.90     28786.90 32.43 5760.56 17.05
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 5760.56 0.00
Exterior Wall   16831.54     16831.54 18.96 2940.29 19.53
Interzone Wall   -1390.9     -1390.9 -1.6 2940.29 -1.6
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 2940.29 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -15976.8     -15976.8 -18.0 5760.56 -9.5
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 5221.01       5221.01 5.88 24.02 741.51
Fenestration Solar   4638.28     4638.28 5.22 24.02 658.75
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 33628.70 41645.45 0.00 13497.49 88771.65      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 17:00:00
Outside Dry Bulb Temperature [F] 86.55
Outside Wet Bulb Temperature [F] 73.22
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 73.99
Zone Relative Humidity [%] 54.86
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00981
Supply Air Temperature [F] 53.99
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 3515.99
Outside Air Flow [ft3/min] 1114.17
Peak Sensible Load with Sizing Factor [Btu/h] 86337.07
Difference Due to Sizing Factor [Btu/h] 11261.36
Peak Sensible Load [Btu/h] 75075.71
Estimated Instant + Delayed Sensible Load [Btu/h] 75274.15
Difference Between Peak and Estimated Sensible Load [Btu/h] -198.4


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.3169
Airflow per Floor Area [ft3/min-ft2] 6.105E-01
Airflow per Total Capacity [ft3-h/min-Btu] 3.784E-03
Floor Area per Total Capacity [ft2-h/Btu] 6.672E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.499E+01
Number of People 38.4


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 5760.56 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 5760.56 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 5760.56 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 5760.56 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 5760.56 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -31094.3     -5679.6 -36773.9 40.95 2940.29 -42.7
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -27171.2     -27171.2 30.26 5760.56 -16.1
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 5760.56 0.00
Exterior Wall   -17762.2     -17762.2 19.78 2940.29 -20.6
Interzone Wall   1830.10     1830.10 -2.0 2940.29 2.12
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 2940.29 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   -3966.6     -3966.6 4.42 5760.56 -2.3
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction -5962.5       -5962.5 6.64 24.02 -846.8
Fenestration Solar   0.00     0.00 -0.00 24.02 0.00
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -37056.8 -47069.9 0.00 -5679.6 -89806.3      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.32
Outside Wet Bulb Temperature [F] 0.32
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 71.99
Zone Relative Humidity [%] 22.36
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00370
Supply Air Temperature [F] 52.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 3978.23
Outside Air Flow [ft3/min] 1114.17
Peak Sensible Load with Sizing Factor [Btu/h] -105216.1
Difference Due to Sizing Factor [Btu/h] -21043.2
Peak Sensible Load [Btu/h] -84172.8
Estimated Instant + Delayed Sensible Load [Btu/h] -84126.7
Difference Between Peak and Estimated Sensible Load [Btu/h] -46.1


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.2801
Airflow per Floor Area [ft3/min-ft2] 6.907E-01
Airflow per Total Capacity [ft3-h/min-Btu] -3.513E-03
Floor Area per Total Capacity [ft2-h/Btu] -5.475E-02
Total Capacity per Floor Area [Btu/h-ft2] -1.826E+01
Number of People 38.4



Table of Contents

Report: Zone Component Load Summary

For: BLOCK1:ZONE2XVAV

Timestamp: 2024-05-02 13:51:58

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 5525.10 1208.28   4889.28 11622.66 15.20 4800.47 8.26
Lights 982.65 4492.22 0.00   5474.87 7.16 4800.47 3.89
Equipment 13102.07 1671.40   0.00 14773.46 19.32 4800.47 10.50
Refrigeration 0.00   0.00 0.00 0.00 0.00 4800.47 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 4800.47 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 4063.24     6404.81 10468.06 13.69 3300.32 10.82
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   25566.60     25566.60 33.43 4800.47 18.17
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 4800.47 0.00
Exterior Wall   13927.22     13927.22 18.21 3300.32 14.40
Interzone Wall   -519.5     -519.5 -0.7 900.09 -2.0
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 3300.32 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -14079.3     -14079.3 -18.4 4800.47 -10.0
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 3807.25       3807.25 4.98 81.54 159.31
Fenestration Solar   5431.32     5431.32 7.10 81.54 227.27
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 27480.31 37698.27 0.00 11294.10 76472.68      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 17:00:00
Outside Dry Bulb Temperature [F] 86.55
Outside Wet Bulb Temperature [F] 73.22
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 73.99
Zone Relative Humidity [%] 54.70
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00978
Supply Air Temperature [F] 53.99
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 3042.08
Outside Air Flow [ft3/min] 928.48
Peak Sensible Load with Sizing Factor [Btu/h] 74700.03
Difference Due to Sizing Factor [Btu/h] 9743.48
Peak Sensible Load [Btu/h] 64956.54
Estimated Instant + Delayed Sensible Load [Btu/h] 65178.58
Difference Between Peak and Estimated Sensible Load [Btu/h] -222.0


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.3052
Airflow per Floor Area [ft3/min-ft2] 6.338E-01
Airflow per Total Capacity [ft3-h/min-Btu] 3.784E-03
Floor Area per Total Capacity [ft2-h/Btu] 6.426E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.556E+01
Number of People 32.0


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 4800.47 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 4800.47 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 4800.47 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 4800.47 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 4800.47 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -25911.9     -4785.0 -30696.9 36.51 3300.32 -31.7
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -22319.6     -22319.6 26.54 4800.47 -15.9
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 4800.47 0.00
Exterior Wall   -19313.0     -19313.0 22.97 3300.32 -20.0
Interzone Wall   842.77     842.77 -1.0 900.09 3.19
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 3300.32 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   -4252.4     -4252.4 5.06 4800.47 -3.0
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction -8347.2       -8347.2 9.93 81.54 -349.3
Fenestration Solar   0.00     0.00 -0.00 81.54 0.00
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -34259.1 -45042.3 0.00 -4785.0 -84086.4      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.32
Outside Wet Bulb Temperature [F] 0.32
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 71.99
Zone Relative Humidity [%] 22.56
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00373
Supply Air Temperature [F] 52.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 3749.83
Outside Air Flow [ft3/min] 928.48
Peak Sensible Load with Sizing Factor [Btu/h] -99175.3
Difference Due to Sizing Factor [Btu/h] -19835.1
Peak Sensible Load [Btu/h] -79340.3
Estimated Instant + Delayed Sensible Load [Btu/h] -79301.4
Difference Between Peak and Estimated Sensible Load [Btu/h] -38.9


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.2476
Airflow per Floor Area [ft3/min-ft2] 7.813E-01
Airflow per Total Capacity [ft3-h/min-Btu] -3.513E-03
Floor Area per Total Capacity [ft2-h/Btu] -4.840E-02
Total Capacity per Floor Area [Btu/h-ft2] -2.066E+01
Number of People 32.0



Table of Contents

Report: Zone Component Load Summary

For: BLOCK1:ZONE4XVAV

Timestamp: 2024-05-02 13:51:58

Estimated Cooling Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 7217.18 1554.36   6386.60 15158.15 15.06 6270.61 8.25
Lights 1283.59 5773.34 0.00   7056.93 7.01 6270.61 3.84
Equipment 17114.58 2150.13   0.00 19264.71 19.14 6270.61 10.48
Refrigeration 0.00   0.00 0.00 0.00 0.00 6270.61 0.00
Water Use Equipment 0.00     0.00 0.00 0.00 6270.61 0.00
HVAC Equipment Losses 0.00 0.00     0.00 0.00    
Power Generation Equipment 0.00 0.00     0.00 0.00    
DOAS Direct to Zone 0.00     0.00 0.00 0.00    
Infiltration 5307.64     8371.80 13679.44 13.59 3885.38 12.01
Zone Ventilation 0.00     0.00 0.00 0.00    
Interzone Mixing 0.00     0.00 0.00 0.00    
Roof   33104.58     33104.58 32.89 6270.61 18.01
Interzone Ceiling   0.00     0.00 0.00 0.00  
Other Roof   0.00     0.00 0.00 6270.61 0.00
Exterior Wall   12947.22     12947.22 12.86 3885.38 11.37
Interzone Wall   -648.0     -648.0 -0.6 1035.10 -2.1
Ground Contact Wall   0.00     0.00 0.00 0.00  
Other Wall   0.00     0.00 0.00 3885.38 0.00
Exterior Floor   0.00     0.00 0.00 0.00  
Interzone Floor   0.00     0.00 0.00 0.00  
Ground Contact Floor   -16441.0     -16441.0 -16.3 6270.61 -8.9
Other Floor   0.00     0.00 0.00 0.00  
Fenestration Conduction 7836.44       7836.44 7.78 200.56 133.32
Fenestration Solar   8708.12     8708.12 8.65 200.56 148.15
Opaque Door   0.00     0.00 0.00 0.00  
Grand Total 38759.42 47148.74 0.00 14758.40 100666.56      


Cooling Peak Conditions

Value
Time of Peak Load 6/15 17:00:00
Outside Dry Bulb Temperature [F] 86.55
Outside Wet Bulb Temperature [F] 73.22
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.01451
Zone Dry Bulb Temperature [F] 73.99
Zone Relative Humidity [%] 54.67
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00977
Supply Air Temperature [F] 53.99
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 4007.65
Outside Air Flow [ft3/min] 1212.82
Peak Sensible Load with Sizing Factor [Btu/h] 98409.94
Difference Due to Sizing Factor [Btu/h] 12836.08
Peak Sensible Load [Btu/h] 85573.86
Estimated Instant + Delayed Sensible Load [Btu/h] 85908.16
Difference Between Peak and Estimated Sensible Load [Btu/h] -334.3


Engineering Checks for Cooling

Value
Outside Air Fraction [fraction] 0.3026
Airflow per Floor Area [ft3/min-ft2] 6.392E-01
Airflow per Total Capacity [ft3-h/min-Btu] 3.784E-03
Floor Area per Total Capacity [ft2-h/Btu] 6.372E-02
Total Capacity per Floor Area [Btu/h-ft2] 1.569E+01
Number of People 41.8


Estimated Heating Peak Load Components

Sensible - Instant [Btu/h] Sensible - Delayed [Btu/h] Sensible - Return Air [Btu/h] Latent [Btu/h] Total [Btu/h] %Grand Total Related Area [ft2] Total per Area [Btu/h-ft2]
People 0.00 0.00   0.00 0.00 -0.00 6270.61 0.00
Lights 0.00 0.00 0.00   0.00 -0.00 6270.61 0.00
Equipment 0.00 0.00   0.00 0.00 -0.00 6270.61 0.00
Refrigeration 0.00   0.00 0.00 0.00 -0.00 6270.61 0.00
Water Use Equipment 0.00     0.00 0.00 -0.00 6270.61 0.00
HVAC Equipment Losses 0.00 0.00     0.00 -0.00    
Power Generation Equipment 0.00 0.00     0.00 -0.00    
DOAS Direct to Zone 0.00     0.00 0.00 -0.00    
Infiltration -33847.4     -6244.1 -40091.4 36.92 3885.38 -35.2
Zone Ventilation 0.00     0.00 0.00 -0.00    
Interzone Mixing 0.00     0.00 0.00 -0.00    
Roof   -29128.6     -29128.6 26.83 6270.61 -15.8
Interzone Ceiling   0.00     0.00 -0.00 0.00  
Other Roof   0.00     0.00 -0.00 6270.61 0.00
Exterior Wall   -21640.4     -21640.4 19.93 3885.38 -19.0
Interzone Wall   979.60     979.60 -0.9 1035.10 3.23
Ground Contact Wall   0.00     0.00 -0.00 0.00  
Other Wall   0.00     0.00 -0.00 3885.38 0.00
Exterior Floor   0.00     0.00 -0.00 0.00  
Interzone Floor   0.00     0.00 -0.00 0.00  
Ground Contact Floor   -4993.3     -4993.3 4.60 6270.61 -2.7
Other Floor   0.00     0.00 -0.00 0.00  
Fenestration Conduction -13704.9       -13704.9 12.62 200.56 -233.2
Fenestration Solar   0.00     0.00 -0.00 200.56 0.00
Opaque Door   0.00     0.00 -0.00 0.00  
Grand Total -47552.3 -54782.7 0.00 -6244.1 -108579.0      


Heating Peak Conditions

Value
Time of Peak Load 1/15 24:00:00
Outside Dry Bulb Temperature [F] 0.32
Outside Wet Bulb Temperature [F] 0.32
Outside Humidity Ratio at Peak [lbWater/lbAir] 0.00082
Zone Dry Bulb Temperature [F] 71.99
Zone Relative Humidity [%] 22.54
Zone Humidity Ratio at Peak [lbWater/lbAir] 0.00373
Supply Air Temperature [F] 52.00
Mixed Air Temperature [F]  
Main Fan Air Flow [ft3/min] 4839.02
Outside Air Flow [ft3/min] 1212.82
Peak Sensible Load with Sizing Factor [Btu/h] -127982.1
Difference Due to Sizing Factor [Btu/h] -25596.4
Peak Sensible Load [Btu/h] -102385.7
Estimated Instant + Delayed Sensible Load [Btu/h] -102335.0
Difference Between Peak and Estimated Sensible Load [Btu/h] -50.7


Engineering Checks for Heating

Value
Outside Air Fraction [fraction] 0.2506
Airflow per Floor Area [ft3/min-ft2] 7.719E-01
Airflow per Total Capacity [ft3-h/min-Btu] -3.513E-03
Floor Area per Total Capacity [ft2-h/Btu] -4.900E-02
Total Capacity per Floor Area [Btu/h-ft2] -2.041E+01
Number of People 41.8



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 89.78 23.04 73.40 Wetbulb [F] 0.00 0.00
WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 0.32 0.00 0.32 Wetbulb [F] 393.72 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BLOCK1:ZONE1XCAV_WALL_4_0_0 WHEELER WALL R-10 0.30 0.100 0.109 2550.25 2550.25 270.00 90.00 W
BLOCK1:ZONE1XCAV_WALL_5_0_0 WHEELER WALL R-10 0.30 0.100 0.109 540.05 540.05 180.00 90.00 S
BLOCK1:ZONE1XCAV_GROUNDFLOOR_0_0_0 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 1 1.00 0.025 0.025 6120.60 6120.60 0.00 180.00  
BLOCK1:ZONE1XCAV_ROOF_1_0_0 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 6120.60 6120.60 180.00 0.00  
BLOCK1:ZONE5_WALL_3_0_0 WHEELER WALL R-10 0.30 0.100 0.109 135.01 135.01 0.00 90.00 N
BLOCK1:ZONE5_WALL_6_0_0 WHEELER WALL R-10 0.30 0.100 0.109 240.02 216.02 0.00 90.00 N
BLOCK1:ZONE5_WALL_8_0_0 WHEELER WALL R-10 0.30 0.100 0.109 150.01 135.01 270.00 90.00 W
BLOCK1:ZONE5_WALL_10_0_0 WHEELER WALL R-10 0.30 0.100 0.109 375.04 337.53 180.00 90.00 S
BLOCK1:ZONE5_WALL_13_0_0 WHEELER WALL R-10 0.30 0.100 0.109 135.01 135.01 180.00 90.00 S
BLOCK1:ZONE5_GROUNDFLOOR_0_0_0 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 2 1.00 0.012 0.012 1210.12 1210.12 0.00 180.00  
BLOCK1:ZONE5_GROUNDFLOOR_0_0_1 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 2 1.00 0.012 0.012 3060.30 3060.30 0.00 180.00  
BLOCK1:ZONE5_ROOF_1_0_0 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 1210.12 1210.12 180.00 0.00  
BLOCK1:ZONE5_ROOF_1_0_1 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 3060.30 3060.30 180.00 0.00  
BLOCK1:ZONE3_WALL_2_0_0 WHEELER WALL R-10 0.30 0.100 0.109 5100.50 5100.50 90.00 90.00 E
BLOCK1:ZONE3_WALL_3_0_0 WHEELER WALL R-10 0.30 0.100 0.109 600.06 600.06 0.00 90.00 N
BLOCK1:ZONE3_WALL_5_0_0 WHEELER WALL R-10 0.30 0.100 0.109 600.06 600.06 180.00 90.00 S
BLOCK1:ZONE3_GROUNDFLOOR_0_0_0 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 3 1.00 0.023 0.023 13601.33 13601.33 0.00 180.00  
BLOCK1:ZONE3_ROOF_1_0_0 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 13601.33 13601.33 180.00 0.00  
BLOCK1:ZONE6XCAV_WALL_3_0_0 WHEELER WALL R-10 0.30 0.100 0.109 540.05 540.05 0.00 90.00 N
BLOCK1:ZONE6XCAV_WALL_4_0_0 WHEELER WALL R-10 0.30 0.100 0.109 2400.23 2160.21 270.00 90.00 W
BLOCK1:ZONE6XCAV_GROUNDFLOOR_0_0_0 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 4 1.00 0.025 0.025 5760.56 5760.56 0.00 180.00  
BLOCK1:ZONE6XCAV_ROOF_1_0_0 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 5760.56 5760.56 180.00 0.00  
BLOCK1:ZONE2XVAV_WALL_2_0_0 WHEELER WALL R-10 0.30 0.100 0.109 1200.12 1080.11 90.00 90.00 E
BLOCK1:ZONE2XVAV_WALL_4_0_0 WHEELER WALL R-10 0.30 0.100 0.109 1200.12 1080.11 270.00 90.00 W
BLOCK1:ZONE2XVAV_WALL_5_0_0 WHEELER WALL R-10 0.30 0.100 0.109 900.09 810.08 180.00 90.00 S
BLOCK1:ZONE2XVAV_GROUNDFLOOR_0_0_0 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 5 1.00 0.033 0.034 4800.47 4800.47 0.00 180.00  
BLOCK1:ZONE2XVAV_ROOF_1_0_0 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 4800.47 4800.47 180.00 0.00  
BLOCK1:ZONE4XVAV_WALL_2_0_0 WHEELER WALL R-10 0.30 0.100 0.109 1200.12 1080.11 90.00 90.00 E
BLOCK1:ZONE4XVAV_WALL_3_0_0 WHEELER WALL R-10 0.30 0.100 0.109 1035.10 931.59 0.00 90.00 N
BLOCK1:ZONE4XVAV_WALL_4_0_0 WHEELER WALL R-10 0.30 0.100 0.109 300.03 270.03 270.00 90.00 W
BLOCK1:ZONE4XVAV_WALL_5_0_0 WHEELER WALL R-10 0.30 0.100 0.109 225.02 202.52 0.00 90.00 N
BLOCK1:ZONE4XVAV_WALL_6_0_0 WHEELER WALL R-10 0.30 0.100 0.109 750.07 525.05 270.00 90.00 W
BLOCK1:ZONE4XVAV_WALL_7_0_0 WHEELER WALL R-10 0.30 0.100 0.109 225.02 202.52 180.00 90.00 S
BLOCK1:ZONE4XVAV_WALL_8_0_0 WHEELER WALL R-10 0.30 0.100 0.109 150.01 135.01 270.00 90.00 W
BLOCK1:ZONE4XVAV_GROUNDFLOOR_0_0_0 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 6 1.00 0.030 0.031 750.07 750.07 0.00 180.00  
BLOCK1:ZONE4XVAV_GROUNDFLOOR_0_0_1 CZ5 NON-RES SLAB-ON-GRADE FLOOR UNHEATED R-0 (0.0) F-.73 (1.264) - 6 1.00 0.030 0.031 5520.54 5520.54 0.00 180.00  
BLOCK1:ZONE4XVAV_ROOF_1_0_0 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 750.07 750.07 180.00 0.00  
BLOCK1:ZONE4XVAV_ROOF_1_0_1 CZ5 NON-RES ROOF INS ENTIRELY ABOVE DECK R-15C.I. (2.6C.I.) U-0.063 (0.358) [2016 TABLE G3.4] 0.30 0.063 0.066 5520.54 5520.54 180.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BLOCK1:ZONE1XCAV_PARTITION_2_0_0 PROJECT PARTITION 0.50 0.299 0.503 2550.25 2550.25 90.00 90.00 E
BLOCK1:ZONE1XCAV_PARTITION_3_0_0 PROJECT PARTITION 0.50 0.299 0.503 540.05 540.05 0.00 90.00 N
BLOCK1:ZONE5_PARTITION_12_0_10000 PROJECT PARTITION_REV 0.50 0.299 0.503 2550.25 2550.25 270.00 90.00 W
BLOCK1:ZONE5_PARTITION_11_0_10001 PROJECT PARTITION_REV 0.50 0.299 0.503 540.05 540.05 180.00 90.00 S
BLOCK1:ZONE5_PARTITION_2_0_0 PROJECT PARTITION 0.50 0.299 0.503 5100.50 5100.50 90.00 90.00 E
BLOCK1:ZONE5_PARTITION_4_0_0 PROJECT PARTITION 0.50 0.299 0.503 2400.23 2400.23 270.00 90.00 W
BLOCK1:ZONE5_PARTITION_5_0_0 PROJECT PARTITION 0.50 0.299 0.503 540.05 540.05 0.00 90.00 N
BLOCK1:ZONE5_PARTITION_7_0_0 PROJECT PARTITION 0.50 0.299 0.503 1035.10 1035.10 0.00 90.00 N
BLOCK1:ZONE5_PARTITION_9_0_0 PROJECT PARTITION 0.50 0.299 0.503 900.09 900.09 180.00 90.00 S
BLOCK1:ZONE3_PARTITION_4_0_10002 PROJECT PARTITION_REV 0.50 0.299 0.503 5100.50 5100.50 270.00 90.00 W
BLOCK1:ZONE6XCAV_PARTITION_2_0_10003 PROJECT PARTITION_REV 0.50 0.299 0.503 2400.23 2400.23 90.00 90.00 E
BLOCK1:ZONE6XCAV_PARTITION_5_0_10004 PROJECT PARTITION_REV 0.50 0.299 0.503 540.05 540.05 180.00 90.00 S
BLOCK1:ZONE2XVAV_PARTITION_3_0_10006 PROJECT PARTITION_REV 0.50 0.299 0.503 900.09 900.09 0.00 90.00 N
BLOCK1:ZONE4XVAV_PARTITION_9_0_10005 PROJECT PARTITION_REV 0.50 0.299 0.503 1035.10 1035.10 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
BLOCK1:ZONE5_WALL_6_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 20.90 2.50 0.60 24.00 24.00 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE5_WALL_6_0_0 0.00 90.00 N
BLOCK1:ZONE5_WALL_8_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 12.49 2.02 0.48 15.00 15.00 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE5_WALL_8_0_0 270.00 90.00 W
BLOCK1:ZONE5_WALL_10_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 33.50 3.22 0.78 37.50 37.50 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE5_WALL_10_0_0 180.00 90.00 S
BLOCK1:ZONE6XCAV_WALL_4_0_0_0_0_8_WIN WHEELER PROJECT - U-0.5 - 1001 23.38 2.65 0.64 26.67 240.02 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE6XCAV_WALL_4_0_0 270.00 90.00 W
BLOCK1:ZONE2XVAV_WALL_2_0_0_0_0_3_WIN WHEELER PROJECT - U-0.5 - 1001 26.50 2.82 0.68 30.00 120.01 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE2XVAV_WALL_2_0_0 90.00 90.00 E
BLOCK1:ZONE2XVAV_WALL_4_0_0_0_0_3_WIN WHEELER PROJECT - U-0.5 - 1001 26.50 2.82 0.68 30.00 120.01 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE2XVAV_WALL_4_0_0 270.00 90.00 W
BLOCK1:ZONE2XVAV_WALL_5_0_0_0_0_2_WIN WHEELER PROJECT - U-0.5 - 1001 26.50 2.82 0.68 30.00 90.01 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE2XVAV_WALL_5_0_0 180.00 90.00 S
BLOCK1:ZONE4XVAV_WALL_2_0_0_0_0_3_WIN WHEELER PROJECT - U-0.5 - 1001 26.50 2.82 0.68 30.00 120.01 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_2_0_0 90.00 90.00 E
BLOCK1:ZONE4XVAV_WALL_3_0_0_0_0_3_WIN WHEELER PROJECT - U-0.5 - 1001 22.65 2.60 0.63 25.88 103.51 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_3_0_0 0.00 90.00 N
BLOCK1:ZONE4XVAV_WALL_4_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 26.50 2.82 0.68 30.00 30.00 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_4_0_0 270.00 90.00 W
BLOCK1:ZONE4XVAV_WALL_5_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 19.49 2.42 0.58 22.50 22.50 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_5_0_0 0.00 90.00 N
BLOCK1:ZONE4XVAV_WALL_6_0_0_0_0_2_WIN WHEELER PROJECT - U-0.5 - 1001 68.50 5.22 1.28 75.01 225.02 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_6_0_0 270.00 90.00 W
BLOCK1:ZONE4XVAV_WALL_7_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 19.49 2.42 0.58 22.50 22.50 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_7_0_0 180.00 90.00 S
BLOCK1:ZONE4XVAV_WALL_8_0_0_0_0_0_WIN WHEELER PROJECT - U-0.5 - 1001 12.49 2.02 0.48 15.00 15.00 0.501 0.551 0.901 1.673 1.673 No BLOCK1:ZONE4XVAV_WALL_8_0_0 270.00 90.00 W
Total or Average           1185.12 0.501 0.551 0.901              
North Total or Average           150.01 0.501 0.551 0.901              
Non-North Total or Average           1035.10 0.501 0.551 0.901              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
BLOCK1:ZONE1XCAV GENERAL LIGHTING BLOCK1:ZONE1XCAV 2.0470 6120.60 12528.77 General ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 56.05 165.72 55.23 0.0000 Y 10574.01
BLOCK1:ZONE5 GENERAL LIGHTING BLOCK1:ZONE5 2.0470 4270.42 8741.48 General ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 56.05 165.72 55.23 0.0000 Y 7377.62
BLOCK1:ZONE3 GENERAL LIGHTING BLOCK1:ZONE3 2.0470 13601.33 27841.72 General ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 56.05 165.72 55.23 0.0000 Y 23497.79
BLOCK1:ZONE6XCAV GENERAL LIGHTING BLOCK1:ZONE6XCAV 2.0470 5760.56 11791.79 General ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 56.05 165.72 55.23 0.0000 Y 9952.01
BLOCK1:ZONE2XVAV GENERAL LIGHTING BLOCK1:ZONE2XVAV 2.0470 4800.47 9826.49 General ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 56.05 165.72 55.23 0.0000 Y 8293.34
BLOCK1:ZONE4XVAV GENERAL LIGHTING BLOCK1:ZONE4XVAV 2.0470 6270.61 12835.85 General ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 56.05 165.72 55.23 0.0000 Y 10833.18
Interior Lighting Total   2.0470 40823.98 83566.11               70527.94


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
Exterior Lighting Total 0.00           0.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BOILER Boiler:HotWater 883883.59 0.85    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
AIR LOOP - RTU VAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed   429352.88 301012.10 128340.78 0.70 3.00    
AIR LOOP - RTU CAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed   399808.74 280299.20 119509.54 0.70 3.00    
AIR LOOP - ERU CAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed   584267.31 409620.01 174647.30 0.70 3.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
AIR LOOP - RTU VAV AHU UNITARY COOLING COIL DX COOLING COIL   34.7 2.66 9.07 9.63 9.11 9.52
AIR LOOP - RTU CAV AHU UNITARY COOLING COIL DX COOLING COIL   32.3 2.66 9.07 9.63 9.11 9.52
AIR LOOP - ERU CAV AHU UNITARY COOLING COIL DX COOLING COIL   47.2 2.66 9.07 9.63 9.11 9.52
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
AIR LOOP - RTU VAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed                
AIR LOOP - RTU CAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed                
AIR LOOP - ERU CAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
BLOCK1:ZONE2XVAV SINGLE DUCT VAV REHEAT HEATING COIL Coil:Heating:Water 158587.80 117799.61 -
BLOCK1:ZONE4XVAV SINGLE DUCT VAV REHEAT HEATING COIL Coil:Heating:Water 204651.28 152015.88 -
AIR LOOP - RTU VAV AHU HEATING COIL Coil:Heating:Fuel   120645.68 0.80
AIR LOOP - RTU CAV AHU HEATING COIL Coil:Heating:Fuel   414545.86 0.80
AIR LOOP - ERU CAV AHU HEATING COIL Coil:Heating:Fuel   613214.10 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
AIR LOOP - RTU VAV AHU EXTRACT FAN Fan:VariableVolume 0.60 0.06 10736.06 3473.21 0.32 1.00 1.35 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00
AIR LOOP - RTU VAV AHU SUPPLY FAN Fan:VariableVolume 0.60 0.12 10736.06 6946.17 0.65 1.00 1.19 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00
AIR LOOP - RTU CAV AHU EXTRACT FAN Fan:ConstantVolume 0.60 0.06 9997.30 3234.22 0.32 1.00 1.36 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00
AIR LOOP - RTU CAV AHU SUPPLY FAN Fan:ConstantVolume 0.60 0.12 9997.30 6468.20 0.65 1.00 1.20 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00
AIR LOOP - ERU CAV AHU EXTRACT FAN Fan:ConstantVolume 0.60 0.06 14609.73 4726.38 0.32 1.00 1.33 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00
AIR LOOP - ERU CAV AHU SUPPLY FAN Fan:ConstantVolume 0.60 0.12 14609.73 9452.41 0.65 1.00 1.18 General WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
DHW LOOP SUPPLY PUMP Pump:VariableSpeed Intermittent 2.90 2.534107 4.55 1.80 0.90 General
HW LOOP SUPPLY PUMP Pump:VariableSpeed Intermittent 2.90 99.800514 179.37 1.80 0.90 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
DHW LOOP WATER HEATER WaterHeater:Mixed 12.20 96922.10 0.80 0.41 0.72



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
BLOCK1:ZONE1XCAV 72179.93 83006.92 13.56 3380.375 3887.431 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 73.99 73.99 0.00988 86.55 0.01451 1183.809 0.00
BLOCK1:ZONE5 57860.35 66539.40 15.58 2709.751 3116.214 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 73.99 73.99 0.00978 86.55 0.01451 825.958 0.00
BLOCK1:ZONE3 149548.49 171980.76 12.64 7003.747 8054.309 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 16:30:00 73.99 73.99 0.00994 87.48 0.01451 2630.686 0.00
BLOCK1:ZONE6XCAV 75075.71 86337.07 14.99 3515.992 4043.391 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 73.99 73.99 0.00981 86.55 0.01451 1114.173 0.00
BLOCK1:ZONE2XVAV 64956.54 74700.03 15.56 3042.085 3498.398 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 73.99 73.99 0.00978 86.55 0.01451 928.478 0.00
BLOCK1:ZONE4XVAV 85573.86 98409.94 15.69 4007.648 4608.795 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 73.99 73.99 0.00977 86.55 0.01451 1212.824 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
BLOCK1:ZONE1XCAV 85048.41 106310.51 17.37 4019.612 5024.515 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 72.00 71.99 0.00369 0.32 0.00082 1183.809 0.00
BLOCK1:ZONE5 61860.06 77325.08 18.11 2923.670 3654.587 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 72.00 71.99 0.00370 0.32 0.00082 825.958 0.00
BLOCK1:ZONE3 185434.29 231792.87 17.04 8764.113 10955.142 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 72.00 71.99 0.00368 0.32 0.00082 2630.686 0.00
BLOCK1:ZONE6XCAV 84172.84 105216.05 18.26 3978.230 4972.788 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 72.00 71.99 0.00370 0.32 0.00082 1114.173 0.00
BLOCK1:ZONE2XVAV 79340.25 99175.31 20.66 3749.829 4687.287 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 72.00 71.99 0.00373 0.32 0.00082 928.478 0.00
BLOCK1:ZONE4XVAV 102385.72 127982.15 20.41 4839.019 6048.773 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 72.00 71.99 0.00373 0.32 0.00082 1212.824 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
AIR LOOP - RTU VAV 8107.19 8107.19 10736.06 10736.06 8107.1924 10736.0600 10736.0600 1.0000 0.3000
AIR LOOP - RTU CAV 7930.82 7930.82 9997.30 9997.30 9997.3025 9997.3025 9997.3025 1.0000 1.0000
AIR LOOP - ERU CAV 11156.29 11156.29 14609.73 14609.73 14609.7284 14609.7284 14609.7284 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
BLOCK1:ZONE2XVAV SINGLE DUCT VAV REHEAT HEATING COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BLOCK1:ZONE2XVAV SINGLE DUCT VAV REHEAT ADU 158587.799 158587.799 1406.185979 2.39321306 1813.798 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 158587.80 158587.80 1406.185979 60.01 54.42 0.00800000 91.99 59.87 0.00400000 0.32 0.00082200 0.32 0.0000 71.99 0.00373320 21.8788 99175.31 0.00 115106.15 115106.15
BLOCK1:ZONE4XVAV SINGLE DUCT VAV REHEAT HEATING COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BLOCK1:ZONE4XVAV SINGLE DUCT VAV REHEAT ADU 204651.284 204651.284 1814.632032 3.08834682 2340.634 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 204651.28 204651.28 1814.632032 60.01 54.42 0.00800000 91.99 59.87 0.00400000 0.32 0.00082200 0.32 0.0000 71.99 0.00373021 21.8614 127982.15 0.00 148540.07 148540.07
AIR LOOP - RTU VAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC AIR LOOP - RTU VAV 429352.877 301012.098 0.107361E+05 -999. -999.00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 16:40:00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 422391.64 280669.93 0.107361E+05 77.49 65.42 0.01103759 50.29 50.29 0.00800000 87.17 0.01451168 72.74 19.9449 73.99 0.00977912 53.0736 150070.79 0.00 429563.71 297196.95
AIR LOOP - RTU VAV AHU HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIR LOOP - RTU VAV 120645.683 120645.683 -999. -999. -999.00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 01:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 120645.68 120645.68 3220.818011 24.34 21.45 0.00179715 60.01 54.42 0.00800000 0.32 0.00082200 0.32 66.4832 71.99 0.00373144 21.8686 181671.40 0.00 -999.0 -999.0
AIR LOOP - RTU CAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC AIR LOOP - RTU CAV 399808.736 280299.196 9997.302497 -999. -999.00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 16:50:00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 17:00:00 390320.87 255432.68 9997.302497 77.74 65.73 0.01120481 50.35 50.35 0.00800000 86.86 0.01451136 72.65 22.9860 73.99 0.00984753 53.4390 147255.65 0.00 400005.06 276746.57
AIR LOOP - RTU CAV AHU HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIR LOOP - RTU CAV 414545.861 414545.861 -999. -999. -999.00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 414545.86 414545.86 9997.302497 55.52 42.65 0.00303425 95.00 66.77 0.00800000 0.32 0.00082200 0.32 22.9860 71.99 0.00369453 21.6535 169221.25 0.00 -999.0 -999.0
AIR LOOP - ERU CAV AHU UNITARY COOLING COIL DX COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC AIR LOOP - ERU CAV 584267.313 409620.009 0.146097E+05 -999. -999.00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 15:20:00 SUMMER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) JUN 6/15 16:50:00 572737.46 373787.44 0.146097E+05 78.81 66.28 0.01135615 50.37 50.37 0.00800000 89.32 0.01451386 73.33 23.6599 73.99 0.00990661 53.7543 205314.61 0.00 584554.22 404428.32
AIR LOOP - ERU CAV AHU HEATING COIL Coil:Heating:Fuel AirLoopHVAC AIR LOOP - ERU CAV 613214.102 613214.102 -999. -999. -999.00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 WINTER DESIGN DAY IN BRYANT GEOTHERMAL (01-01:31-12) 1/15 24:00:00 613214.10 613214.10 0.146097E+05 55.04 42.36 0.00300873 95.00 66.77 0.00800000 0.32 0.00082200 0.32 23.6599 71.99 0.00368646 21.6065 247294.36 0.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BLOCK1:ZONE1XCAV 352.67 2051.17 48.50
BLOCK1:ZONE5 206.50 2061.50 8.50
BLOCK1:ZONE3 239.17 2056.83 11.00
BLOCK1:ZONE6XCAV 402.17 2021.00 50.17
BLOCK1:ZONE2XVAV 1054.83 2094.33 739.67
BLOCK1:ZONE4XVAV 1089.83 2091.33 769.00
Facility 1132.17 2154.67 793.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BLOCK1:ZONE1XCAV 0.00 0.67 0.00 0.00
BLOCK1:ZONE5 0.00 0.00 0.00 0.00
BLOCK1:ZONE3 0.00 0.00 0.00 0.00
BLOCK1:ZONE6XCAV 0.00 0.67 0.00 0.00
BLOCK1:ZONE2XVAV 1439.83 0.00 189.50 0.00
BLOCK1:ZONE4XVAV 1493.00 0.00 205.83 0.00
Facility 1494.33 0.67 206.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
BLOCK1:ZONE1XCAV 36.11 40.82 91813.44 0.769 0.260 0.000 0.000
BLOCK1:ZONE5 25.19 28.48 64059.38 0.825 0.260 0.000 0.000
BLOCK1:ZONE3 80.24 90.72 204029.87 0.777 0.260 0.000 0.000
BLOCK1:ZONE6XCAV 33.98 38.42 86412.65 0.809 0.260 0.000 0.000
BLOCK1:ZONE2XVAV 28.32 32.02 72010.54 0.791 0.259 0.000 0.000
BLOCK1:ZONE4XVAV 36.99 41.83 94063.77 0.781 0.259 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
BLOCK1:ZONE1XCAV 36.11 40.82 91813.44 0.750 0.005 0.000 0.000
BLOCK1:ZONE5 25.19 28.48 64059.38 0.803 0.005 0.000 0.000
BLOCK1:ZONE3 80.24 90.72 204029.87 0.757 0.005 0.000 0.000
BLOCK1:ZONE6XCAV 33.98 38.42 86412.65 0.788 0.005 0.000 0.000
BLOCK1:ZONE2XVAV 28.32 32.02 72010.54 0.607 0.005 0.000 0.000
BLOCK1:ZONE4XVAV 36.99 41.83 94063.77 0.696 0.005 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Surfaces by Class

Total Outdoors
Wall 36 22
Floor 8 8
Roof 8 8
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 14 14
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 6
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1109
Defaulted Fields 142
Fields with Defaults 2675
Autosized Fields 92
Autosizable Fields 102
Autocalculated Fields 66
Autocalculatable Fields 158



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
Electricity:Building 207044.28 0.00 01-JAN-00:10 60821.60 02-JAN-08:10
Electricity:Zone:BLOCK1:ZONE1XCAV 31041.43 0.00 01-JAN-00:10 9118.77 02-JAN-08:10
InteriorLights:Electricity 70527.94 0.00 01-JAN-00:10 22042.64 02-JAN-08:10
InteriorLights:Electricity:Zone:BLOCK1:ZONE1XCAV 10574.01 0.00 01-JAN-00:10 3304.78 02-JAN-08:10
General:InteriorLights:Electricity 70527.94 0.00 01-JAN-00:10 22042.64 02-JAN-08:10
Electricity:Zone:BLOCK1:ZONE5 21657.99 0.00 01-JAN-00:10 6362.28 02-JAN-08:10
InteriorLights:Electricity:Zone:BLOCK1:ZONE5 7377.62 0.00 01-JAN-00:10 2305.78 02-JAN-08:10
Electricity:Zone:BLOCK1:ZONE3 68980.94 0.00 01-JAN-00:10 20263.93 02-JAN-08:10
InteriorLights:Electricity:Zone:BLOCK1:ZONE3 23497.79 0.00 01-JAN-00:10 7343.95 02-JAN-08:10
Electricity:Zone:BLOCK1:ZONE6XCAV 29215.46 0.00 01-JAN-00:10 8582.37 02-JAN-08:10
InteriorLights:Electricity:Zone:BLOCK1:ZONE6XCAV 9952.01 0.00 01-JAN-00:10 3110.38 02-JAN-08:10
Electricity:Zone:BLOCK1:ZONE2XVAV 24346.22 0.00 01-JAN-00:10 7151.98 02-JAN-08:10
InteriorLights:Electricity:Zone:BLOCK1:ZONE2XVAV 8293.34 0.00 01-JAN-00:10 2591.98 02-JAN-08:10
Electricity:Zone:BLOCK1:ZONE4XVAV 31802.25 0.00 01-JAN-00:10 9342.27 02-JAN-08:10
InteriorLights:Electricity:Zone:BLOCK1:ZONE4XVAV 10833.18 0.00 01-JAN-00:10 3385.78 02-JAN-08:10
InteriorEquipment:Electricity 136516.34 0.00 01-JAN-00:10 38778.96 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BLOCK1:ZONE1XCAV 20467.42 0.00 01-JAN-00:10 5813.99 02-JAN-08:10
General:InteriorEquipment:Electricity 136516.34 0.00 01-JAN-00:10 38778.96 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BLOCK1:ZONE5 14280.37 0.00 01-JAN-00:10 4056.50 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BLOCK1:ZONE3 45483.15 0.00 01-JAN-00:10 12919.99 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BLOCK1:ZONE6XCAV 19263.45 0.00 01-JAN-00:10 5471.99 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BLOCK1:ZONE2XVAV 16052.88 0.00 01-JAN-00:10 4560.00 02-JAN-08:10
InteriorEquipment:Electricity:Zone:BLOCK1:ZONE4XVAV 20969.07 0.00 01-JAN-00:10 5956.49 02-JAN-08:10
ElectricityPurchased:Facility 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
ElectricityPurchased:Plant 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
Cogeneration:ElectricityPurchased 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
General:Cogeneration:ElectricityPurchased 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
ElectricityNet:Plant 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
Cogeneration:ElectricityNet 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
General:Cogeneration:ElectricityNet 383809.06 0.00 08-APR-13:10 194708.13 01-AUG-14:10
Electricity:HVAC 176659.89 0.00 01-JAN-00:40 133885.02 01-AUG-14:10
Fans:Electricity 101613.44 0.00 01-JAN-00:40 34291.20 06-JUN-13:40
General:Fans:Electricity 101613.44 0.00 01-JAN-00:40 34291.20 06-JUN-13:40
Cooling:Electricity 75046.45 0.00 01-JAN-00:40 99593.83 01-AUG-14:10
General:Cooling:Electricity 75046.45 0.00 01-JAN-00:40 99593.83 01-AUG-14:10
Heating:Electricity 20.06 0.00 02-JAN-18:10 14.45 16-FEB-08:00
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Plant 104.89 0.00 08-APR-13:10 98.05 16-FEB-08:00
Boiler Parasitic:Heating:Electricity 20.06 0.00 02-JAN-18:10 14.45 16-FEB-08:00
Pumps:Electricity 84.83 0.00 08-APR-13:10 83.60 16-FEB-08:00
General:Pumps:Electricity 84.83 0.00 08-APR-13:10 83.60 16-FEB-08:00
WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 16057.14 0.00 02-JAN-18:50 1201927.66 10-JAN-07:10
NaturalGas:HVAC 6334.07 0.00 01-JAN-00:10 987122.43 14-JAN-07:10
Heating:NaturalGas 14018.67 0.00 02-JAN-18:10 1131471.08 10-JAN-08:00
General:Heating:NaturalGas 6334.07 0.00 01-JAN-00:10 987122.43 14-JAN-07:10
NaturalGas:Plant 9723.07 0.00 02-JAN-18:50 640945.75 16-FEB-08:00
Boiler:Heating:NaturalGas 7684.60 0.00 02-JAN-18:10 575123.34 16-FEB-08:00
WaterSystems:NaturalGas 2038.46 0.00 01-JAN-00:10 142189.98 14-FEB-12:50
Water Heater:WaterSystems:NaturalGas 2038.46 0.00 01-JAN-00:10 142189.98 14-FEB-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
Water:Plant 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
WaterSystems:Water 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
General:WaterSystems:Water 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
MainsWater:Facility 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
MainsWater:Plant 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
WaterSystems:MainsWater 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
General:WaterSystems:MainsWater 31961.76 0.00 01-JAN-00:10 0.19 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 4398704.99 0.00 08-APR-13:10 1864956.96 10-JAN-08:00
EnergyTransfer:Building 1404395.80 0.00 02-JAN-18:10 696860.35 14-JAN-05:10
EnergyTransfer:Zone:BLOCK1:ZONE1XCAV 218793.55 0.00 02-JAN-18:10 117030.31 14-JAN-05:10
Heating:EnergyTransfer 945511.22 0.00 02-JAN-18:10 696860.35 14-JAN-05:10
Heating:EnergyTransfer:Zone:BLOCK1:ZONE1XCAV 145356.63 0.00 02-JAN-14:00 117030.31 14-JAN-05:10
General:Heating:EnergyTransfer 945511.22 0.00 02-JAN-18:10 696860.35 14-JAN-05:10
Cooling:EnergyTransfer 458884.59 0.00 01-JAN-00:10 437476.70 02-AUG-16:00
Cooling:EnergyTransfer:Zone:BLOCK1:ZONE1XCAV 73436.91 0.00 01-JAN-00:10 62541.73 02-AUG-16:00
General:Cooling:EnergyTransfer 458884.59 0.00 01-JAN-00:10 437476.70 02-AUG-16:00
EnergyTransfer:Zone:BLOCK1:ZONE5 156231.43 0.00 02-JAN-18:10 85787.43 14-JAN-05:10
Heating:EnergyTransfer:Zone:BLOCK1:ZONE5 101644.93 0.00 02-JAN-18:10 85787.43 14-JAN-05:10
Cooling:EnergyTransfer:Zone:BLOCK1:ZONE5 54586.50 0.00 01-JAN-00:10 49066.67 02-AUG-16:00
EnergyTransfer:Zone:BLOCK1:ZONE3 478490.62 0.00 02-JAN-18:10 255198.66 14-JAN-05:10
Heating:EnergyTransfer:Zone:BLOCK1:ZONE3 313955.65 0.00 02-JAN-18:10 255198.66 14-JAN-05:10
Cooling:EnergyTransfer:Zone:BLOCK1:ZONE3 164534.97 0.00 01-JAN-00:10 136956.40 02-AUG-16:00
EnergyTransfer:Zone:BLOCK1:ZONE6XCAV 218525.46 0.00 02-JAN-18:10 114098.42 10-JAN-05:10
Heating:EnergyTransfer:Zone:BLOCK1:ZONE6XCAV 146015.18 0.00 02-JAN-14:00 114098.42 10-JAN-05:10
Cooling:EnergyTransfer:Zone:BLOCK1:ZONE6XCAV 72510.28 0.00 01-JAN-00:10 63090.01 02-AUG-16:00
EnergyTransfer:Zone:BLOCK1:ZONE2XVAV 143987.75 0.00 01-JAN-00:40 57228.58 14-JAN-04:50
Heating:EnergyTransfer:Zone:BLOCK1:ZONE2XVAV 103009.39 0.00 01-JAN-00:40 57228.58 14-JAN-04:50
Cooling:EnergyTransfer:Zone:BLOCK1:ZONE2XVAV 40978.37 0.00 01-JAN-00:10 54834.94 02-AUG-16:00
EnergyTransfer:Zone:BLOCK1:ZONE4XVAV 188366.99 0.00 01-JAN-00:40 74416.11 14-JAN-04:50
Heating:EnergyTransfer:Zone:BLOCK1:ZONE4XVAV 135529.44 0.00 01-JAN-00:40 74416.11 14-JAN-04:50
Cooling:EnergyTransfer:Zone:BLOCK1:ZONE4XVAV 52837.55 0.00 01-JAN-00:10 70986.95 02-AUG-16:00
EnergyTransfer:HVAC 2144318.79 0.00 02-JAN-18:10 1139659.21 10-JAN-08:00
HeatingCoils:EnergyTransfer 811164.80 0.00 01-JAN-00:40 924438.61 10-JAN-08:00
PlantLoopHeatingDemand:Facility 852646.57 0.00 08-APR-13:10 520882.53 16-FEB-08:00
PlantLoopHeatingDemand:HVAC 712386.17 0.00 02-JAN-18:10 510029.97 16-FEB-08:00
HeatingCoils:PlantLoopHeatingDemand 304439.21 0.00 01-JAN-00:40 135771.18 10-JAN-08:00
Baseboard:EnergyTransfer 301029.59 0.00 02-JAN-05:10 299163.73 16-FEB-08:00
Baseboard:PlantLoopHeatingDemand 407946.96 0.00 02-JAN-05:10 404478.47 16-FEB-08:00
CoolingCoils:EnergyTransfer 846105.51 0.00 01-JAN-00:40 1061602.53 03-JUL-16:00
HeatRecoveryForHeating:EnergyTransfer 174534.43 0.00 01-JAN-00:10 215220.60 10-JAN-08:00
HeatRecoveryForCooling:EnergyTransfer 11484.46 0.00 01-JAN-00:10 99285.24 03-JUL-10:00
EnergyTransfer:Plant 849990.40 0.00 08-APR-13:10 521666.50 16-FEB-08:00
Boilers:EnergyTransfer 709730.00 0.00 02-JAN-18:10 510813.94 16-FEB-08:00
WaterSystems:EnergyTransfer 140260.40 0.00 01-JAN-00:10 58031.43 12-FEB-12:40
General:WaterSystems:EnergyTransfer 140260.40 0.00 01-JAN-00:10 58031.43 12-FEB-12:40
PlantLoopHeatingDemand:Plant 140260.40 0.00 01-JAN-00:10 58031.43 12-FEB-12:40
WaterSystems:PlantLoopHeatingDemand 140260.40 0.00 01-JAN-00:10 58031.43 12-FEB-12:40
General:WaterSystems:PlantLoopHeatingDemand 140260.40 0.00 01-JAN-00:10 58031.43 12-FEB-12:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
BLOCK1:ZONE1XCAV 62377.558 0.000 82978.932 -6115.52 0.000 0.000 22356.766 36104.074 69884.307 0.000 0.000 1472.763 0.000 0.000 0.000 0.000 -90497.60 -111241.51
BLOCK1:ZONE5 39960.303 0.000 61684.673 -4545.76 0.000 0.000 15681.242 25190.262 48759.151 4373.402 0.000 1018.993 0.000 0.000 -4699.69 0.000 -63228.01 -74154.78
BLOCK1:ZONE3 134824.312 0.000 179131.394 -13701.87 0.000 0.000 49619.906 80231.273 155298.455 0.000 0.000 3412.670 0.000 0.000 0.000 0.000 -200935.86 -237049.74
BLOCK1:ZONE6XCAV 63867.417 0.000 82147.629 -6038.35 0.000 0.000 21093.460 33980.304 65773.465 9143.240 0.000 1351.705 0.000 0.000 -15489.29 0.000 -85205.78 -104153.54
BLOCK1:ZONE2XVAV 0.000 0.000 103008.557 -3412.42 0.000 0.000 18684.655 28316.921 54811.222 26510.783 0.000 1226.754 0.000 0.000 -17522.31 0.000 -65391.24 -108668.98
BLOCK1:ZONE4XVAV 0.000 0.000 135528.343 -4399.97 0.000 0.000 24434.159 36988.980 71597.163 34463.275 0.000 1602.220 0.000 0.000 -29063.18 0.000 -85277.05 -137438.99
Total Facility 301029.591 0.000 644479.529 -38213.88 0.000 0.000 151870.189 240811.814 466123.764 74490.700 0.000 10085.105 0.000 0.000 -66774.47 0.000 -590535.54 -772707.53


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
BLOCK1:ZONE1XCAV 23-AUG-00:37 0.00 0.00 0.00 -7.2 0.00 0.00 0.00 626.44 6264.43 0.00 0.00 0.00 82387.75 0.00 0.00 0.00 -2419.4 0.00
BLOCK1:ZONE5 15-AUG-22:10 0.00 0.00 0.00 -5.3 0.00 0.00 0.00 437.07 1456.92 0.00 0.00 0.00 62004.29 0.00 -80.4 0.00 -516.0 0.00
BLOCK1:ZONE3 04-AUG-11:27 0.00 0.00 0.00 -15.9 0.00 0.00 0.00 1392.09 4640.32 0.00 0.00 7008.64 177681.22 0.00 0.00 0.00 0.00 0.00
BLOCK1:ZONE6XCAV 01-JUN-15:20 0.00 0.00 0.00 -7.2 0.00 0.00 0.00 1768.77 1965.31 10741.53 0.00 0.00 73386.13 0.00 0.00 0.00 -1146.0 0.00
BLOCK1:ZONE2XVAV 02-AUG-17:43 0.00 0.00 0.00 -6.8 0.00 0.00 0.00 2947.95 1637.76 12459.22 0.00 2223.36 62784.58 0.00 0.00 0.00 0.00 0.00
BLOCK1:ZONE4XVAV 02-AUG-17:43 0.00 0.00 0.00 -8.9 0.00 0.00 0.00 3850.76 2139.32 27383.78 0.00 2848.68 70551.26 0.00 0.00 0.00 0.00 0.00
Total Facility 09-AUG-17:15 0.00 0.00 0.00 -47.5 0.00 0.00 0.00 25069.83 13927.77 49623.73 0.00 5819.57 475657.60 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
BLOCK1:ZONE1XCAV 07-MAY-04:01 0.00 0.00 130530.81 0.00 0.00 0.00 0.00 1252.88 6264.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -5551.1 -132497.0
BLOCK1:ZONE5 27-DEC-06:05 10472.98 0.00 88606.45 0.00 0.00 0.00 0.00 874.15 4370.77 0.00 0.00 0.00 0.00 0.00 -1310.4 0.00 -13854.8 -89159.2
BLOCK1:ZONE3 07-MAY-04:01 0.00 0.00 284694.77 0.00 0.00 0.00 0.00 2784.17 13920.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -12325.2 -289074.7
BLOCK1:ZONE6XCAV 07-MAY-04:01 0.00 0.00 128988.52 0.00 0.00 0.00 0.00 1179.18 5895.93 0.00 0.00 0.00 0.00 0.00 -1152.8 0.00 -5238.9 -129671.9
BLOCK1:ZONE2XVAV 14-JAN-04:50 0.00 0.00 57228.37 0.00 0.00 0.00 0.00 491.32 4913.28 0.00 0.00 0.00 0.00 0.00 -6849.3 0.00 -19800.8 -35982.9
BLOCK1:ZONE4XVAV 14-JAN-04:50 0.00 0.00 74415.83 0.00 0.00 0.00 0.00 641.79 6417.97 0.00 0.00 0.00 0.00 0.00 -11189.8 0.00 -25725.3 -44560.5
Total Facility 14-JAN-05:02 0.00 0.00 754954.61 0.00 0.00 0.00 0.00 8356.61 41783.31 0.00 0.00 0.00 0.00 0.00 -26992.0 0.00 -201567.0 -576535.6



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AIR LOOP - RTU VAV 10736.0600 0.0000 73.8448 1.0000 2141.3014 8107.1924 1.0000 1.0000 2141.3014 0.2641    
AIR LOOP - RTU CAV 9997.3025 0.0000 79.2481 1.0000 2297.9818 9997.3025 1.0000 1.0000 2297.9818 0.2299    
AIR LOOP - ERU CAV 14609.7284 0.0000 119.2057 1.0000 3456.6444 14609.7284 1.0000 1.0000 3456.6444 0.2366    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
AIR LOOP - RTU VAV 3220.8180 0.0000 73.8448 1.0000 2141.3014 3220.8180 0.1994 1.0000 2141.3014 0.6648    
AIR LOOP - RTU CAV 9997.3025 0.0000 79.2481 1.0000 2297.9818 9997.3025 0.2299 1.0000 2297.9818 0.2299    
AIR LOOP - ERU CAV 14609.7284 0.0000 119.2057 1.0000 3456.6444 14609.7284 0.2366 1.0000 3456.6444 0.2366    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
BLOCK1:ZONE1XCAV AIR LOOP - RTU CAV 19.997879 40.8248 0.060039 6120.60 1183.8088 1.0000 1183.8088 1.000 1183.8088
BLOCK1:ZONE5 AIR LOOP - ERU CAV 19.997879 28.4840 0.060039 4270.42 825.9582 1.0000 825.9582 1.000 825.9582
BLOCK1:ZONE3 AIR LOOP - ERU CAV 19.997879 90.7217 0.060039 13601.33 2630.6862 1.0000 2630.6862 1.000 2630.6862
BLOCK1:ZONE6XCAV AIR LOOP - RTU CAV 19.997879 38.4233 0.060039 5760.56 1114.1730 1.0000 1114.1730 1.000 1114.1730
BLOCK1:ZONE2XVAV AIR LOOP - RTU VAV 19.997879 32.0194 0.060039 4800.47 928.4775 1.0000 928.4775 1.000 928.4775
BLOCK1:ZONE4XVAV AIR LOOP - RTU VAV 19.997879 41.8254 0.060039 6270.61 1212.8238 1.0000 1212.8238 1.000 1212.8238


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
AIR LOOP - RTU VAV 19.997879 73.84 0.060039 11071.0810 2141.3014 2141.3014 2141.3014
AIR LOOP - RTU CAV 19.997879 79.25 0.060039 11881.1594 2297.9818 2297.9818 2297.9818
AIR LOOP - ERU CAV 19.997879 119.21 0.060039 17871.7439 3456.6444 3456.6444 3456.6444


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BLOCK1:ZONE1XCAV AIR LOOP - RTU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5024.5147 5024.5147 5024.5147 1183.8088 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE5 AIR LOOP - ERU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 3654.5869 3654.5869 3654.5869 825.9582 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE3 AIR LOOP - ERU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 10955.1415 10955.1415 10955.1415 2630.6862 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE6XCAV AIR LOOP - RTU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4972.7878 4972.7878 4972.7878 1114.1730 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE2XVAV AIR LOOP - RTU VAV AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4687.2866 4687.2866 1406.1860 928.4775 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE4XVAV AIR LOOP - RTU VAV AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6048.7734 6048.7734 1814.6320 1212.8238 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
AIR LOOP - RTU VAV 10736.0600 8107.1924 10736.0600 3220.8180 2141.3014 1.0000
AIR LOOP - RTU CAV 9997.3025 9997.3025 9997.3025 9997.3025 2297.9818 1.0000
AIR LOOP - ERU CAV 14609.7284 14609.7284 14609.7284 14609.7284 3456.6444 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BLOCK1:ZONE1XCAV AIR LOOP - RTU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5024.5147 5024.5147 5024.5147 1183.8088 0.2356 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE5 AIR LOOP - ERU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 3654.5869 3654.5869 3654.5869 825.9582 0.2260 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE3 AIR LOOP - ERU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 10955.1415 10955.1415 10955.1415 2630.6862 0.2401 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE6XCAV AIR LOOP - RTU CAV AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4972.7878 4972.7878 4972.7878 1114.1730 0.2241 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE2XVAV AIR LOOP - RTU VAV AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1406.1860 1406.1860 1406.1860 928.4775 0.1981 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BLOCK1:ZONE4XVAV AIR LOOP - RTU VAV AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1814.6320 1814.6320 1814.6320 1212.8238 0.2005 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
AIR LOOP - RTU VAV 3220.8180 3220.8180 3220.8180 3220.8180 2141.3014 1.0000
AIR LOOP - RTU CAV 9997.3025 9997.3025 9997.3025 9997.3025 2297.9818 1.0000
AIR LOOP - ERU CAV 14609.7284 14609.7284 14609.7284 14609.7284 3456.6444 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-05-02 13:51:58

Sec1.1A-General Information

Data
Weather File BRYANT GEOTHERMAL (01-01:31-12) ** Ann Arbor Municipal MI USA TMY3 WMO#=725374
Total gross floor area [ft2] 40823.98
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
BLOCK1:ZONE1XCAV 6120.60 6120.60 0.00 49.29
BLOCK1:ZONE5 4270.42 4270.42 0.00 49.29
BLOCK1:ZONE3 13601.33 13601.33 0.00 49.29
BLOCK1:ZONE6XCAV 5760.56 5760.56 0.00 49.29
BLOCK1:ZONE2XVAV 4800.47 4800.47 0.00 49.29
BLOCK1:ZONE4XVAV 6270.61 6270.61 0.00 49.29
Totals 40823.98 40823.98 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 206.00
Number of hours cooling loads not met 0.00
Number of hours not met 206.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 6334.07 987122.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 7684.60 575123.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 20.06 14.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 75046.45 99593.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 70527.94 22042.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- General 136516.34 38778.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 101613.44 34291.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 84.83 83.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 2038.46 142189.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 466123.76 1310484.28
Natural Gas 0.00 1605713.76
Additional 0.00 0.00
Total 466123.76 2916198.04


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 1.73
Space Heating 0.00
Space Cooling 1.84
Fans (All) 2.49
Service Water Heating 0.00
Receptacle Equipment 3.34
Miscellaneous (All) 9.40
Subtotal 9.40


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 10.06
Service Water Heating 1.46
Miscellaneous (All) 11.52
Subtotal 11.52


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.26
Space Heating 48.07
Space Cooling 8.79
Fans (All) 11.90
Service Water Heating 6.99
Receptacle Equipment 15.98
Miscellaneous 0.01


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
7:00 - 18:00 MON - FRI 2871. 2871.
ASHRAE 90.1 LIGHTING RECEPTACLE - OFFICE 2922. 8760.
ASHRAE 90.1 SERVICE HOT WATER - OFFICE 1595. 8760.
COOLING FRACTION SCHEDULE 8760. 8760.
HEATING FRACTION SCHEDULE 8760. 8760.
COMMUNITY MH OCCUPANCY 2284. 2610.
COMM MH HVAC AVAIL 3393. 3393.
WHEELER CENTER - EDIT OF RECEPTACLE - ASHRAE 90.1 OCCUPANCY - OFFICE 3395. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
BLOCK1:ZONE2XVAV HEATING SETPOINT SCHEDULE BLOCK1:ZONE2XVAV DUAL SP January 72.00 365 70.00 365
BLOCK1:ZONE2XVAV COOLING SETPOINT SCHEDULE BLOCK1:ZONE2XVAV DUAL SP July 73.99 365 75.99 365
BLOCK1:ZONE4XVAV HEATING SETPOINT SCHEDULE BLOCK1:ZONE4XVAV DUAL SP January 72.00 365 70.00 365
BLOCK1:ZONE4XVAV COOLING SETPOINT SCHEDULE BLOCK1:ZONE4XVAV DUAL SP July 73.99 365 75.99 365
BLOCK1:ZONE1XCAV HEATING SETPOINT SCHEDULE BLOCK1:ZONE1XCAV DUAL SP January 72.00 365 70.00 365
BLOCK1:ZONE1XCAV COOLING SETPOINT SCHEDULE BLOCK1:ZONE1XCAV DUAL SP July 73.99 365 75.99 365
BLOCK1:ZONE6XCAV HEATING SETPOINT SCHEDULE BLOCK1:ZONE6XCAV DUAL SP January 72.00 365 70.00 365
BLOCK1:ZONE6XCAV COOLING SETPOINT SCHEDULE BLOCK1:ZONE6XCAV DUAL SP July 73.99 365 75.99 365
BLOCK1:ZONE5 HEATING SETPOINT SCHEDULE BLOCK1:ZONE5 DUAL SP January 72.00 365 70.00 365
BLOCK1:ZONE5 COOLING SETPOINT SCHEDULE BLOCK1:ZONE5 DUAL SP July 73.99 365 75.99 365
BLOCK1:ZONE3 HEATING SETPOINT SCHEDULE BLOCK1:ZONE3 DUAL SP January 72.00 365 70.00 365
BLOCK1:ZONE3 COOLING SETPOINT SCHEDULE BLOCK1:ZONE3 DUAL SP July 73.99 365 75.99 365